Mitsubishi Electric MELSEC Q Series User Manual page 69

Programmabale web server module
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS
Signal Direction Web server module
Programmable controller CPU
Device
No.
ERR. LED status
X10
ON: On, Flicker
Tag collection error
X11
ON: Error occurrence
Logging error
X12
ON: Error occurrence
CPU event monitor error
X13
ON: Error occurrence
Tag event monitor error
X14
ON: Error occurrence
Time event monitor error
X15
ON: Error occurrence
Access target CPU error
X16
ON: Error occurrence
E-mail transmission error
X17
ON: Error occurrence
FTP transfer error
X18
ON: Error occurrence
Connection error
X19
ON: Error occurrence
X1A
Use prohibited
X1B
Other error
X1C
ON: Error occurrence
X1D
Use prohibited
X1E
Watchdog timer error
X1F
ON: Error occurrence
3 - 13
Signal name
OFF: Off
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
OFF: Normal
Important
Do not output (turn on) the signal marked "use prohibited" among the I/O signals for
the programmable controller CPU.
Doing so can cause malfunction of the programmable controller system.
Signal Direction Programmable controller CPU
Web server module
Device
No.
Error clear request
Y10
ON: Error clear requested OFF:
Y11
Y12
Y13
Y14
Y15
Y16
Y17
Use prohibited
Y18
Y19
Y1A
Y1B
Y1C
Y1D
Y1E
Y1F
MELSEC-Q
Signal name
3 - 13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec qj71ws96

Table of Contents