9 TROUBLE SHOOTING
Error
Error name
code
Setting update time-out
0618h
error
0619h
Device name error
File access stopped
0620h
error
0621h
No CF card error
9 - 30
Error definition
Since the module load is too high
the time for setting update ran out.
The device name specified in the
device monitor or device test is
faulty or that of an unusable
device.
At start-up or setting update, the
following was detected.
 Operation involving file writing
was attempted during file access
stop.
At other than start-up or setting
update, the following was detected
in the logging function, event
monitor function or dedicated
instruction.
 Operation involving file writing
was attempted during file access
stop.
At other than start-up or setting
update, the following was detected
in the dedicated instruction.
 Operation involving file writing
was attempted during file access
stop.
At start-up or setting update, the
following was detected.
 Accessing the CF card was
attempted with no CF card set.
At other than start-up or setting
update, the following was detected
in the logging function or
dedicated instruction.
 Accessing the CF card was
attempted with no CF card set.
At other than start-up or setting
update, the following was detected
in the dedicated instruction, or
user display parts.
 Accessing the CF card was
attempted with no CF card set.
(From the previous page)
Corrective action
 Update the setting again.
 Reduce the load for
tag/logging/event monitor
function and reset the CPU
module.
 Refer to the accessible device list
and enter the device name.
(Refer to Appendix 2)
 Turn on File access stop cancel
request (Y3), and execute again
after File access status (X2) has
turned off.
(Refer to Section 3.6.2 (X2))
 Execute after setting the CF card.
(Refer to Section 4.9)
(Continued on the next page)
MELSEC-Q
Error type
Display
Display
Stop
Continue
Display
Stop
Continue
Display
9 - 30