9 TROUBLE SHOOTING
Symptom
An old administrative
menu screen is
displayed. (Display data
are improper.)
Devices are not
monitored. (Display data
are improper.)
Tags are not monitored.
(Display data are
improper.)
Logging file cannot be
opened.
Unable to operate on
the logging monitor
screen
Monitoring stops during
monitor operation.
Run time error occurred.
Too many "HTTP login"
records registered to the
access log
9 - 4
Check point
Check if temporary Internet files have been
deleted.
The access target CPU setting is not correct.
The access target CPU setting is not correct.
Tag setting is not correct.
The file stored on the Web server module is
opened directly with the Open file button on
the logging monitor screen.
The screens such as message screen are
hidden under the active window.
Correct connection has not been established.
®
TM
Microsoft
InterDev
6.0 (Visual Studio
6.0) has been installed.
The personal computer was switched to the
standby or hibernation status during monitor
operation.
If "Debug?" is displayed, select "No".
Check the statuses of the connection devices
such as a modem, cables and the line.
Button or other operation was performed
before the complete screen was displayed.
In the intelligent function module switch
setting, bit 5 (Access log (HTTP login)
registration inhibit setting) of switch 2 is not
set to ON.
Corrective action
 Delete the temporary Internet files of the
Web browser and JAVA VM. Then display
the menu screen again. (Refer to Section
6.2.7 (1) (e).)
 Check the access target CPU setting.
(Refer to Section 4.6.7)
 Check the access target CPU setting.
(Refer to Section 4.6.7)
 Check the tag setting. (Refer to Section
6.3.3)
 If the screen to enter the user name and
the password is displayed, cancel it.
®
 Use Microsoft
 When using Microsoft
open the file after saving the file on the
personal computer.
(Refer to Section 6.2.3.)
 Operate on the logging monitor screen after
checking the displayed screens and closing
them.
 Select the displayed monitor screen again
and monitor the system.
 Restart the Web browser and monitor the
system.
 Re-examine the cable connection.
 From [Tools] - [Options] on Microsoft
InterDevTM 6.0, open the Option dialog
box, select [Debugger] - [General], and
®
unmark the "Attach to execution program of
this machine" setting in the Java items.
 When Microsoft
already been uninstalled, reinstall it and
perform the above operation.
 Check the statuses of the connection
devices such as a modem, and the line,
restart the monitor operation.
 Set the setting to avoid the standby or
hibernation status of personal computer.
(Refer to Section 6.2.7 (1) (d).)
 Check the statuses of the connection
devices such as a modem, cables and the
line.
 After deleting the temporary Internet files of
Internet Explorer
 Start operation after the screen display is
completed.
 In the intelligent function module switch
setting, set bit 5 (Access log (HTTP login)
registration inhibit setting) of switch 2 to
ON. (Refer to Section 4.7.)
 Enable the cookies in the browser. (Refer
to Section 4.5 (3) (e).)
(Continued on the next page)
MELSEC-Q
(From the previous page)
Office 2003 or earlier.
®
Office 2007 or later,
®
®
InterDevTM 6.0 has
®
, try to connect again.
9 - 4