5 OPERATION CONTROL PROGRAMS
[Functions]
(1) Conversion of the input value specified with (S2) is executed according to the
search/conversion method specified with (S1), using the scaling conversion data
of device (S3) or later. The conversion result is stored in the device specified with
(D).
(2) The setting method of (S1) is the same as 16-bit integer type scaling. (Refer to
Section 5.16.1.)
(3) The device No. specified with (S3) should be an even number. Set the point data
in the specified device as follows.
Off set
Name
+0
Number of points (N)
+1
Unusable
+2
+3
Point 0
+4
+5
+6
+7
Point 1
+8
+9
+10
+11
Point 2
+12
+13
:
:
+ (4N-2)
+ (4N-1)
Point (N-1)
+ (4N)
+ (4N+1)
POINT
Set the point data corresponding to the input value in ascending order. (Positive
conversion: X
< X
<.....< X
0
1
(4) When the conversion result to be stored in the device specified with (D) is not an
integer value, its fractional portion is rounded down.
Set the number of points for the scaling conversion
data.
Set 0.
X
0
Y
0
X
1
Y
1
Set the point data of (X
X
device No. is in consecutive order.
2
Y
2
X
N-1
Y
N-1
, Inverse conversion: Y
N-1
5 - 150
Description
, Y
) to (X
, Y
) so that the
0
0
N-1
N-1
< Y
<.....< Y
0
1
N-1
Range
2 to 2000
0
-2147483648
to
2147483647
)