iBAT 2.0-CIM01C2
User Manual
Item
Number of battery
strings
Number of iBOXs
iBOX start address
iBOX number of
iBATs
iBOX logical start addr
Current source
Batt. abnormal BCB
trip
Multi-Hall cur. setting
iBOX No.
Issue 07 (2019-01-02)
Figure 5-8 Batt. String Config
UPS WebUI
a.
On the UPS WebUI homepage, choose Param. Settings > Battery Setting, and set
Number of battery strings.
b.
On the UPS WebUI homepage, choose iBOX Settings, and set Basic Param.,
Advanced Param., and Batt. String Config.
Copyright © Huawei Technologies Co., Ltd.
Description
Specifies the number of battery strings connected in parallel.
The number of iBOXs connected to UPS.
Communication address of the iBOX when the UPS queries
iBOX data.
Specifies the number of iBATs managed by the iBOX.
Specifies the communication address when the northbound
device queries iBOX data. When connecting the UPS to the
network management system, do not set iBOX logical start
addr to 0 or a value same as the UPS Address.
Specifications of the Hall effect sensor used to detect iBOX
current.
If the BCB box is configured, set Batt. abnormal BCB trip to
Enable.
Multi-Hall cur. setting is equal to the number of Hall effect
sensors at the positive or negative terminal of a battery string
(Multi-Hall cur. setting ≥ 1).
Set this parameter based on the planned codes for iBOXs.
5 System Commissioning