Huawei iBAT 2.0-CIM01C2 User Manual page 49

Hide thumbs Also See for iBAT 2.0-CIM01C2:
Table of Contents

Advertisement

iBAT 2.0-CIM01C2
User Manual
Parameter
Batt. string No.
Parameter
Parallel
Configuration
Current acquisition
source
Battery N line
Multi-Hall cur.
setting
Total battery
capacity
Batt. installation
time
iBAT Number of
iBOX
Number of battery
strings
Batt. string No.
Parameter
Current acquisition
source
Issue 07 (2019-01-02)
Description
The serial number of each battery string. Under the same CIM, the
battery string numbers must be unique.
V291B028
a.
On the iBOX WebUI home page, choose System Settings > Running Parameter,
and set Parallel Configuration.
b.
On the iBOX WebUI home page, choose System Settings > Batt. String Config,
and set Batt. String Config.
Description
This parameter needs to be set when multiple iBOXs are connected
in parallel and does not need to be set when there is only one iBOX.
Set Parallel Configuration to Parallel, and set iBOX parallel qty..
Configure IP addresses for multiple CIMs.
The actual specifications of the Hall effect sensor prevail.
Set whether there is a battery N wire according to the actual
situation.
The number of positive or negative Hall effect sensors in a single
battery string and should be greater than or equal to 1.
One iBOX: Capacity of one battery string x Number of battery
strings connected in parallel.
N iBOXs connected in parallel: Capacity of one battery string x
(Number of battery strings managed by iBOX 1 + ... + Number
of battery strings managed by iBOX N).
Time when the battery is installed for the first time. Does not need to
be reset when part of batteries are replaced.
Indicates the total number of iBATs managed by the iBOX.
The number of battery strings managed by the iBOX.
The serial number of each battery string. Under the same iBOX, the
battery string numbers must be unique.
V296B019
a.
On the iBOX WebUI, choose System Settings, and set Batt. String Config,
Running Parameter, Time and IP Address.
Description
The actual specifications of the Hall effect sensor prevail.