Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) Ethernet connection type: OP communication
This section describes [Connected Ethernet Controller Setting] when [SIEMENS OP(Ethernet)] is selected for the
model.
Item
Host
Net No.
*1
Station
Unit Type
IP Address
Port No.
Connection No./Rack No.
Module Position/Slot No.
Communication
*1
Set different values for [GOT Station] of [Detail Setting] and [Station] of [Connected Ethernet Controller Setting].
■2. Communication detail settings
*2
The following devices are available to GT21 and GS21.
Description
The host is displayed. (The host is indicated with an asterisk (*).)
Set the network No. of the connected Ethernet module.
(Default: blank)
Set the station No. of the connected Ethernet module.
(Default: blank)
Set the PLC type to be connected.
Set the IP address of the connected Ethernet module.
(Default: blank)
102 (fixed)
Set the Connection No./Rack No. set on the PLC side.
(Default: 0)
Set the Module Position/Slot No. set on the PLC side.
(Default)
S7-200 OP: 0
*2
S7-200 SMART OP:1 (fixed)
S7-300/400 OP: 0
S7-1200 OP: 1 (fixed)
TCP (fixed)
Set value
1 to 239
1 to 254
S7-200 OP
S7-200 SMART OP
S7-300/400 OP
S7-1200 OP
PLC side IP
address
102 (fixed)
S7-200 OP: 0 to 7
S7-200 SMART OP:0 (fixed)
S7-300/400 OP: 0 to 7
S7-1200 OP: 0 (fixed)
S7-200 OP: 0 to 6
S7-200 SMART OP:1 (fixed)
S7-300/400 OP: 0 to 6
S7-1200 OP: 1 (fixed)
TCP (fixed)
15.3 Ethernet Connection
*2
*2
*2
15
15 - 19