4.4.1

FUJI MICREX-F Series

Device name
I/O relay (B)
Auxiliary relay (M)
Keep relay (K)
Special relay (F)
Annunciator relay (A)
Differential relay (D)
Bit device
Link memory (L)
Timer output
(0.01s) (T)
Timer output
(0.1s) (T)
Counter output (C)
Word device bit
I/O relay (WB)
Auxiliary relay (WM)
Keep relay (WK)
Special relay (WF)
Annunciator relay (WA)
Differential relay (WD)
Link memory (WL)
Direct access
*6*7
(W24)
User file (W30)
Word device
User file (W31)
User file (W108)
User file (W109)
Data memory (BD)
Timer set value (0.01s) (TS)
Timer current value (0.01s) (TR)
Timer current value (0.1s) (W9)
Counter set value (CS)
Counter current value (CR)
*1
*2
*3
*4
*5
*6
*7
4 - 38
4.4 Device Range that Can Be Set
*1
*5
*1
*4*6*7
*4*6*7
:
*4*6*7
*4*6*7
*2
*2*3
*2*3
*2*3
*2*3
*2*3
Only reading is possible.
Only 32-bit (2-word) designation is allowed.
Decimal points are not displayed.
To read/write data from/to a user file, set SI data for the data format of the PLC CPU and 16 bits for data length on GT Designer3.
With any setting other than the above, the PLC does not operate normally.
Data format of the PLC CPU
SI (Binary 16-bit length)
DI (Binary 32-bit length)
BD (8-digit BCD)
As bit specification of a word device is performed after the GOT reads the value, do not change the value in the sequence
program during this period.
When it is used with bit specification (bit specification of word device), the offset function cannot be used.
When bit specification (bit specification of word device) is performed, the uppermost bit is b0 and the lowermost bit is b15.
Higher
b0
Setting range
B0000 to B511F
M0000 to M511F
K0000 to K063F
F0000 to F125F
A0000 to A045F
D0000 to D063F
L0000 to L511F
T000 to T511
T512 to T999
C000 to C511
Specified bit of the following word devices
Direct access, user file
WB000 to WB511
WM000 to WM511
WK000 to WK063
WF000 to WF125
WA000 to WA045
WD000 to WD063
WL000 to WL511
W24:0000 to W24:0255
W30:0000 to W30:4095
W31:0000 to W31:4095
W108:0000 to W108:4095
W109:0000 to W109:4095
BD0 to BD4095
TS0 to TS511
TR0 to TR511
W9:0000 to W9:0487
CS0 to CS511
CR0 to CR511
Device data bit: 16 bits
Cannot be used
Cannot be used
b1
b14
:
GT Designer3 setting
Lower
b15
Device No. representation
Decimal + Hexadecimal
Decimal
Decimal
Decimal
Decimal

Advertisement