Plc Side Setting - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal (non-mitsubishi electric products 2)
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(2) SIEMENS S7-200
Item
Transmission Speed
Data Bit
Stop Bit
Parity
Adapter Address
Host Address
15.2.5

PLC Side Setting

PLC CPU
HMI Adapter
PC/PPI cable
15 - 10
15.2 Serial Connection
Set this item when change the transmission speed used for
communication with the connected equipment.
(Default: 19200bps)
Set this item when change the data length used for communication with
the connected equipment.
(Default: 8bits)
Specify the stop bit length for communications.
(Default: 1bit)
Specify whether or not to perform a parity check, and how it is performed
during communication.
(Default: Even)
Specify the adapter address (station No. of the adapter to which the GOT
is connected) in the connected network.
(Default: 0)
Specify the host address (station No. of the PLC that the GOT will monitor)
in the connected network.
(Default: 2)
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be changed on the Utility's [Communication setting]
after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
POINT
POINT
POINT
SIEMENS PLC
For details of SIEMENS PLCs, refer to the following manuals.
SIEMENS PLC user's Manual
Model name
S7-200
6ES7 972-0CA11-0XA0
6ES7 901-3BF20-0XA0
6ES7 901-3CB30-0XA0
Description
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 31
1 to 31
Refer to
15.2.7
15.2.6
15.2.7