■2. Communication detail settings
Make the settings according to the usage environment.
Item
GOT Net No.
*1
GOT Station
GOT Communication Port No.
Retry
Startup Time
Timeout Time
Delay Time
*1
Set different values for [GOT Station] of [Detail Setting] and [Station] of [Connected Ethernet Controller Setting].
➠ ■4.
*2
When assigning the same driver to the multiple channels, in the communication drivers set as the second and following, the
default value of [GOT Communication Port No.] becomes the earliest number in the vacant numbers of No. 6000 and later.
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 18)
Set the GOT port No. for the connection with the Ethernet module.
*2
(Default: 5016
)
Set the number of retries to be performed when a communication timeout
occurs.
When receiving no response after retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a communication to time out.
(Default: 3sec)
Set the delay time for reducing the load of the network/destination PLC.
(Default: 0ms)
Connected Ethernet Controller Setting
POINT
POINT
POINT
(1) Communication interface setting by the Utility
The communication interface setting can be changed on the Utility's [Communication setting]
after writing [Communication Settings] of project data.
For details on the Utility, refer to the following manual.
➠
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the Utility, the latest setting is effective.
Description
6.3 Ethernet Connection
Range
1 to 239
1 to 64
1024 to 5010, 5014 to 65534
(Except for 5011, 5012, 5013 and
49153 to 4917)
0 to 5times
3 to 255sec
1 to 90sec
0 to 10000(10ms)
6 - 27
6