The LIMIT WORD INV Word includes faults and warnings, which occur when the
output current limit of the drive is exceeded. The current limit protects the drive in
various cases, e.g. integrator overload, high IGBT temperature etc.
Table 19 Limit Word Inv (Actual Signal 02.41)
Bit
0
1
2
3
4
5
6
7
8
9
10
11...15
*Not active with ACS800 default settings.
Fieldbus control
Name
Description
INTEGRAT 200
Current limit at 200% integrator overload. Temperature model is
not active.*
INTEGRAT 150
Current limit at 150% integrator overload. Temperature model is
not active.*
INT LOW FREQ
Current limit at high IGBT temperature with low output frequency
(<10 Hz). Temperature model is not active.*
INTG PP TEMP
Current limit at high IGBT temperature. Temperature model is not
active.*
PP OVER TEMP
Current limit at high IGBT temperature. Temperature model is
active.
PP OVERLOAD
Current limit at high IGBT junction to case temperature.
Temperature model is active.
If the IGBT junction to case temperature continues to rise in spite
of the current limitation, PP OVERLOAD alarm or fault occurs.
See chapter
INV POW LIM
Current limit at inverter output power limit
INV TRIP CUR
Current limit at inverter overcurrent trip limit
OVERLOAD CUR
Maximum inverter overload current limit. See 20.03.
CONT DC CUR
Continuous dc-current limit
CONT OUT CUR
Continuous output current limit (I
Reserved
Fault
tracing.
cont.max
)