ABB ACS800 Series Firmware Manual page 122

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

110
No.
Name/Value
63.09 TENSION CTL ENABL
NOT SEL
YES
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
FIELDBUS
PARAM 63.32
63.10 TENSION SETPOINT
AI1
AI2
AI3
AI5
AI6
FIELDBUS
PARAM 63.33
Actual signals and parameters
Description
Set to "ENABLE" if this is a single position machine and there are no
requirements to ever RUN without tension control.
Set to a DI or FBA option if this is a turret or if there are some
instances where the tension regulation should be ignored in RUN
mode.
Not enabled. The drive is in "pure" speed mode.
Enabled. When the drive is in run, the tension regulation trim is active. 2
Digital input DI2 = 1 enables the regulation trim. Otherwise it is in
"pure" speed mode.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2. Instead of a digital input, the command comes from
06.03
DATASET 1 WORD 3 bit 00. See chapter
Source selected by
63.32
TEN CTRL ENBL PTR.
Selects the signal source for setting the tension setpoint.
Analog input AI1 (voltage).
Analog input AI2 (current).
Analog input AI3 (current).
Analog input AI5 (voltage or current).
Analog input AI6 (voltage or current).
06.04
DATASET 3 WORD 1. See chapter
Source selected by
63.33
TEN SETPT PTR.
Fieldbus
control.
Fieldbus
control.
FbEq
1
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7