ABB ACS800 Series Firmware Manual page 185

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

Fault
Cause
OVER SWFREQ
Switching frequency is too high.
(FF55)
02.19 FW 2 bit 09
PANEL LOSS
Control panel or DriveWindow selected as
active control location for drive has ceased
(5300)
communicating.
02.19 FW 2 bit 13
PARAM CRC
CRC (Cyclic Redundancy Check) error
(6320)
POWERFAIL
INT board powerfail in several inverter units of
parallel connected inverter modules.
(3381)
POWERF INV xx
INT board powerfail in inverter unit of several
parallel connected inverter modules. xx (1...12)
(3381)
refers to inverter module number.
PPCC LINK
Fibre optic link to INT board is faulty.
(5210)
02.19 FW 2 bit 11
PPCC LINK xx
INT board fibre optic connection fault in
inverter unit of several parallel connected
(5210)
inverter modules. xx refers to inverter module
02.19 FW 2 bit 11
number.
PP OVERLOAD
Excessive IGBT junction to case temperature.
This fault protects IGBT(s) and it can be
(5482)
activated by short circuit at output of long
motor cables.
RUN DISABLED
No Run enable signal received.
(FF54)
02.19 FW 2 bit 04
SC INV xx y
Short circuit in inverter unit of several parallel
connected inverter modules. xx (1...12) refers
(2340)
to inverter module number and y refers to
02.18 FW 1 bit 04.
phase (U, V, W).
SHORT CIRC
Short-circuit in motor cable(s) or motor
(2340)
02.18 FW 1 bit 00
Output bridge of converter unit is faulty.
What to Do
Check motor parameter settings (parameter
group
99 START-UP
DATA)
Ensure that ID run has been completed
successfully.
Check panel connection (see appropriate
hardware manual).
Check control panel connector.
Replace control panel in mounting platform.
Check Fault Function parameters.
Check DriveWindow connection.
Switch control board power off and on again.
Reload firmware to control board.
Replace control board.
Check that INT board power cable is
connected.
Check that POW board is working correctly.
Replace INT board.
Check that INT board power cable is
connected.
Check that POW board is working correctly.
Replace INT board.
Check fibre optic cables or galvanic link. With
frame sizes R2-R6 link is galvanic.
If RMIO is powered from external supply,
ensure that supply is on. See parameter 16.09.
Check connection from inverter module Main
Circuit Interface Board, INT to PPCC
Branching Unit, PBU. (Inverter module 1 is
connected to PBU INT1 etc.)
Check motor cables.
Check setting of parameter 16.01. Switch on
signal or check wiring of selected source.
Check motor and motor cable.
Check power semiconductors (IGBTs) of
inverter module.
Check motor and motor cable.
Check there are no power factor correction
capacitors or surge absorbers in motor cable.
Contact ABB representative.
173
Fault tracing