ABB ACS800 Series Firmware Manual page 149

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

No.
Name/Value
USER 1 LOAD
USER 1 SAVE
USER 2 LOAD
USER 2 SAVE
99.03 APPLIC RESTORE
NO
YES
99.05 MOTOR NOM VOLTAGE
½...2 x U
N
99.06 MOTOR NOM CURRENT
1/6...2 x I
2hd
99.07 MOTOR NOM FREQ
8...300 Hz
99.08 MOTOR NOM SPEED
1...18000 rpm
99.09 MOTOR NOM POWER
0...9000 kW
0...9000 Hp
Description
User 1 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the
application.
Save User 1 macro. Stores the current parameter settings and the
motor model.
Note: There are parameters that are not included in the macros. See
99.03
APPLIC RESTORE.
User 2 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the
application.
Save User 2 macro. Stores the current parameter settings and the
motor model.
Note: There are parameters that are not included in the macros. See
99.03
APPLIC RESTORE.
Restores the original settings of the active application macro
APPLICATION MACRO).
- If a standard macro is active, the parameter values are restored to
the default settings (factory settings). Exceptions: parameter settings
in group
99 START-UP DATA
remains unchanged.
- If User Macro 1 or 2 is active, the parameter values are restored to
the last saved values. In addition, the last saved motor model are
restored. Exceptions: Settings of
99.02
APPLICATION MACRO remain unchanged.
Note: The parameter settings and the motor model are restored
according to the same principles when a macro is changed to another.
No restoring.
Restoring.
Defines the nominal motor voltage. Must be equal to the value on the
motor rating plate.
Voltage. Allowed range is 1/2...2 · U
Defines the nominal motor current. Must be equal to the value on the
motor rating plate.
Note: Correct motor run requires that the magnetizing current of the
motor does not exceed 90 percent of the nominal current of the
inverter.
Allowed range: 1/6...2 · I
2hd
Defines the nominal motor frequency.
Nominal frequency (50 or 60 Hz typically)
Defines the nominal motor speed. Must be equal to the value on the
motor rating plate. The motor synchronous speed or another
approximate value must not be given instead!
Note: If the value of 99.08 is changed, the speed limits in group
LIMITS
change automatically as well.
Nominal motor speed.
Defines the nominal motor power. Set exactly as on the motor rating
plate.
Nominal motor power.
remain unchanged. The motor model
16.05
USER MACRO IO CHG and
of the drive.
N
of ACS800.
Actual signals and parameters
137
FbEq
7
8
9
10
(99.02
0
65535
1 = 1 V
10 = 1 A
100 = 1 Hz
20
1 = 1 rpm
10 = 1 kW
10 = 1 Hp

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-u2Acs800-u7Acs800-u4

Table of Contents