ABB ACS800 Series Firmware Manual page 115

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

No.
Name/Value
62.04 ZERO INTEG TIME
NOT SEL
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
FIELDBUS
62.05 RANGE ADJUST
0.0...100.0%
62.06 TRIM REG REL TO
SPD REF MAX
SPD REF ACT
62.07 MIN REF TO REG
0.0...10000.0 rpm
Description
Selects the activation source for forcing the integral part of the PI
controller compensation to be zero. The PI controller will become just
a P controller.
Function not selected.
Digital input DI2 = 1 forces the integration time to zero.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2. Instead of a digital input, the command comes from
06.03
DATASET 1 WORD 3 bit 03. See chapter
Determines the amount of speed correction the PI regulator is allowed
to add. The value entered is scaled to
Example:
If 62.05 Range adjust = 5%
62.06
TRIM REG REL TO = "SPD REF MAX"
11.05
EXT1 REF MAX = 1800 rpm
03.03
DANCER REG OUTPUT = 100%
65.01
MIN CORE DIAMETER is 100 mm
03.13
ROLL DIAMETER (mm) is 1000 mm
Then
25.03
SPEED CORRECTION = 0.05*1800*1*(100/1000) = 9 rpm
Setting range.
Setting this to "SPD REF MAX" multiplies the output of the PI regulator
by
11.05
EXT1 REF MAX. Setting it to "SPD REF ACT" multiplies the
output of the PI regulator by the actual speed reference to the drive.
Selecting "SPD REF MAX" means that the maximum speed correction
is constant, regardless of the drive speed, whereas selecting "SPD
REF ACT" gives a varying maximum that is speed dependant.
Value set by
11.05
EXT1 REF MAXIMUM.
Value set by
11.03
EXT1 REF SELECT with a minimum reference for
scaling of
62.07
MIN REF TO REG.
If
62.06
TRIM REG REL TO is set to "SPD REF ACT" it may be
desired to have a minimum value that the PI regulator is multiplied by;
this minimum value is set here. If the actual speed reference goes
below this parameter, the PI regulator output will no longer be
multiplied by the reference, it will instead be multiplied by this
parameter.
Setting range.
Fieldbus
control.
62.06
TRIM REG REL TO.
Actual signals and parameters
103
FbEq
1
2
3
4
5
6
7
8
9
10
11
12
13
10 = 1%
0
65535
10 = 1 rpm