Table 5 Main Status Word (Actual Signal 02.26)
Bit
Name
0
RDY_ON
1
RDY_RUN
2
RDY_REF
3
TRIPPED
4
OFF_2_STA
5
OFF_3_STA
6
SWC_ON_INHIB
7
ALARM
8
AT_SETPOINT
9
REMOTE
10
ABOVE_LIMIT
11
EXT CTRL LOC
12
EXT RUN
ENABLE
13
AT ZERO SPEED
14
HEARTBEAT
15
Value
STATE/Description
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
READY TO OPERATE.
0
OFF1 ACTIVE.
1
OPERATION ENABLED.
0
OPERATION INHIBITED.
1
FAULT.
0
No fault.
1
OFF2 inactive.
0
OFF2 ACTIVE.
1
OFF3 inactive.
0
OFF3 ACTIVE.
1
SWITCH-ON INHIBITED.
0
1
Warning/Alarm.
0
No Warning/Alarm.
1
OPERATING. Actual value equals reference value (= is within
tolerance limits).
0
Actual value differs from reference value (= is outside
tolerance limits).
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
1
Actual frequency or speed value equals or is greater than
supervision limit (32.02). Valid in both rotation directions
regardless of value of 32.02.
0
Actual frequency or speed value is within supervision limit.
1
External Control Location 2 (EXT2) selected.
0
External Control Location 1 (EXT1) selected.
1
External Run Enable signal received.
0
No External Run Enable received.
1
Abs drive actual speed is zero.
0
Abs drive actual speed is above zero.
1
200 ms square wave.
0
(send back on Main Cmd Word bit 14)
1
Communication error detected by fieldbus adapter module (on
fibre optic channel CH0).
0
Fieldbus adapter (CH0) communication OK.
151
Fieldbus control