76
No.
Name/Value

16 SYS CTRL INPUTS

16.01 RUN ENABLE
YES
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
FIELDBUS
MASTER DRV
16.02 PARAMETER LOCK
OPEN
LOCKED
16.03 PASS CODE
0...32767
16.04 FAULT RESET SEL
NOT SEL
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI10
DI11
DI12
Actual signals and parameters
Description
Run enable, parameter lock, etc.
Sets the run enable signal on, or selects a source for the external run
enable signal. If no run enable signal is on, the drive will not start or
stops if it is running.
Run enable signal is on.
External signal required through digital input DI1. 1 = RUN ENABLE.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1. Instead of a digital input, the selection comes from
06.01
DATASET 1 WORD 1 bit 0. See chapter
The run enable signal comes from the master drive.
Selects the state of the parameter lock. The lock prevents parameter
changing.
The lock is open. Parameter values can be changed.
Locked. Parameter values cannot be changed from the control panel.
The lock can be opened by entering the valid Pass Code.
Selects the pass code for the parameter lock.
Setting 358 opens the lock. The value reverts back to 0 automatically. 1 = 1
Selects the source for the fault reset signal. The signal resets the drive
after a fault trip if the cause of the fault no longer exists.
Fault reset only from the control panel keypad (RESET key).
Reset through digital input DI2 or by control panel:
- If the drive is in external control mode: Reset by a rising edge of DI2
- If the drive is in local control mode: Reset by the RESET key of the
control panel.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
See selection DI2.
FbEq
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Fieldbus
control.
15
0
65535
1
2
3
4
5
6
7
8
9
10
11
12

Hide quick links: