Parameter Window - Gx Staircase Lighting - ABB i-bus KNX Product Manual

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.2.3.2.4

Parameter window - Gx Staircase lighting

The parameter window - Gx Staircase lighting is enabled in parameter window Gx Functions, the
parameter Enable function staircase lighting is set with the option yes.
The DLR/A features a function Staircase lighting which can be triggered and stopped via individual switch
telegrams of the individual lighting groups. For each DLR/A, a Staircase lighting sequence can be
programmed which can be adjusted in the parameter window
Note
The function Staircase lighting is comprised of two scenes. The DLR/A automatically selects the internal
scenes 13 and 14 when the function Staircase lighting is selected. Scenes 13 and 14 can are then
enabled and can be recalled via the corresponding scene communication object. Whereby, groups
parameterized with the function Staircase lighting are controlled by the switch on brightness of the
function Staircase lighting.
For further information see:
In parameter window - Gx Staircase lighting, the reaction to various KNX telegrams such as brightness
value, relative dimming, recall scene and voltage recovery can be parameterized. The reaction to a switch
telegram is not explicitly programmable and responds as follows:
The function Staircase lighting can be triggered by an ON telegram to the communication object Switch or
by activation of the function Staircase lighting of a lighting group. With an OFF telegram to the
communication object Switch, the lighting group is controlled with the basis brightness of the function
Staircase lighting. The function Staircase lighting is in standby mode and is started by a renewed ON
telegram. If the Staircase lighting is already at the switch on value, the staircase lighting time is restarted
(retriggered).
The function Staircase lighting is also started if the lighting group receives a telegram with the value 1
(enabling the additional communication object in parameter window Gx Functions) on the communication
object Stairc. light. activate/status.
90 2CDC507128D0202 | DLR/A 4.8.1.1
Staircase
lighting, page 163
Parameter window
General, page 40.

Advertisement

Table of Contents
loading

Table of Contents