ABB i-bus KNX Product Manual page 152

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
40
This communication object is enabled if in
parameter Select additional function.
Using this communication object, the offset for the master/slave control is activated or deactivated. In this way, for example,
the offset is switched off (deactivated) or switched on (activated) at a determined level of external brightness or by a timer.
With deactivated offset, the slave is controlled with same brightness as the master.
On activated offset, the brightness value of the master has the parameterized percentage applied and the provided to the
slave via communication object Master: Brightness offset
Telegram value:
For further information see:
41
This communication object is enabled if in
enabled.
Using this communication object, the internally set variables (control parameters) in the DALI Light Controller can be read or
defined for the current setpoint.
Hereby, different setpoint settings for lighting control can be set for various applications, e.g. for competition and training
settings in sports centers. The procedure is described in
It is inadvisable to transfer control parameter settings for a setpoint from other rooms, as it is practically excluded that both
rooms have exactly the same reflection properties and brightness relationships. Furthermore, the characteristic, which
controls the lighting, is determined during the automatic artificial lighting calibration. If control parameters for a setpoint value
are still transferred regardless of these facts, it must be assumed that the light control will be inexact (large setpoint
deviations).
Telegram value:
150 2CDC507128D0202 | DLR/A 4.8.1.1
Function
Master: Offset activate
1 = the offset for Master: Brightness offset is activated
0 = the offset for Master: Brightness offset is deactivated
Slave with offset
Control parameter
0 = OFF
...
255 = 100 %
Note
This communication object can be read and written in the ETS.
However, the value of the communication object is not sent automatically on the KNX by the DALI Light
Controller, regardless of whether the T flag is or is not set.
Object name
Group 1
Parameter window Gx
Group, page 63, the option Light control is enabled in
function, page 189
Group 1
Parameter window Gx
Group, page 63, the additional function Light control is
Changing the
setpoint, page 171.
Data type
Flags
1 bit
C, R, W, T
DPT 1.003
1 byte
C, R, W
DPT 5.001