ABB i-bus KNX Product Manual page 45

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
no - acknowledge is not necessary: As soon as the fault is remedied, the DLR/A will reset the fault
message, and it automatically sends the status change in dependence on the parameterization to the
communication object, e.g. Fault lamp. A telegram with the value 0 is sent. The change in the
malfunction state may take up to 45 seconds and depends on the number of connected DALI devices.
yes - acknowledgment required: First of all the communication object Acknowledge faults is enabled.
As soon as the fault is rectified, a telegram with the value 0 is not sent automatically. This fault signal
remains set until the fault is rectified and the fault signal is acknowledged or reset via the
communication object Acknowledge faults. Only then does the corresponding communication object
send its value 0. 
This can be very useful with the detection of sporadic faults or 
results.
"Fault controller supply voltage"
Options:
no: Failure of the light controller supply voltage is not reported to the KNX.
yes: The communication object Fault Controller supply is enabled. As soon as the light controller
supply voltage is interrupted, the communication object Fault Controller supply sends a telegram with
the value 1 on the KNX. The time at which a telegram is sent can be adjusted using the following
parameters:
no
yes
Send
Options:
after a change
after request
after a change or request
after a change: The status is sent via the communication object after a change.
after request: The status is sent after a request by the communication object Request status
values.
after a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.
DLR/A 4.8.1.1 | 2CDC507128D0202 43