ABB i-bus KNX Product Manual page 125

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
continued No. 6
The bit number (bit 0 to bit 15) corresponds to the exponent in the binary system, e.g. bit 8, number 8 corresponds to 2
Bit 0...5:
Bit 6:
Bit 7:
Bit 8...15:
Bit 8:
Bit 9:
Bit 10:
Bit 11:
Bit 12:
Bit 13:
Bit 14:
Bit 15
After a KNX bus voltage recovery (Power On) on the DLR/A, this communication object receives the value FF FF Hex.
After download or light controller supply voltage failure, the previous value called after the KNX bus voltage recovery
remains in the communication object.
For further information see:
Function
corresponds with the information as queried in the communication object Request diagnosis (No. 7).
The content identifies the DALI device or lighting group, for which information has been requested.
determines if a group (value 1) or an individual device (value 0) has been recalled
contains a 0
contains the following coded information concerning the recalled DALI device or recalled lighting
group
Fault lamp:
Value 0 = no fault
Value 1 = fault
Fault ballast:
Value 0 = no fault
Value 1 = fault
status of the device monitoring:
Value 0 = there is no monitoring (the DALI devices are not considered with the
Value 1 = monitoring available
Status function Burn-in
Value 0 = function Burn-in not activated
Value 1 = function Burn-in activated (device or lighting group)
can only assume state OFF and 100 %
Status additional function, slave, light control:
Value 0 = no additional function for the device or the lighting group is activated
Value 1 = the additional function for the device or the lighting group is activated
Block status:
Value 0 = Lighting group is not blocked
Value 1 = Lighting group is blocked
Status forced operation:
Value 0 = Lighting group is not forcibly operated
Value 1 = Lighting group is forcibly operated
Status disable sending of fault alarm: (by group, if selected)
Value 0 = fault alarm is not blocked
Value 1 = fault alarm is blocked
DALI device available: (by device, if selected)
Value 0 = DALI device available
Value 1 = DALI device not available
This information is independent of whether the DALI device is no longer
responding because of a fault, or is completely unavailable.
Code table Diagnostics High byte (No.
Object name
monitoring of the ballast)
6), page 196