ABB i-bus KNX Product Manual page 137

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
No.
23
With this communication object, it is possible to disable the fault messages (lamp or ballast fault) of the DLR/A. If the fault
messages are inhibited, the DLR/A will continue to undertake fault message examination regarding lamp and ballast faults.
During the inhibit, the faults are evaluated but not sent on the KNX. The values of the communication objects are also not
updated.
The latent time of the system can be minimized at low KNX load when the fault messages are inhibited.
When all error messages are enabled, the malfunctions will be sent in accordance with their parameterization. If a fault still
exists after enabling of the error message, this fault is recorded and the information is sent on the KNX in accordance with
the parameterization.
Telegram value:
24
This communication object is always enabled.
Using this communication object, you indicate if the system state does not correspond with the state in the DALI Light
Controller, i.e., there are differences between the group and scene assignments stored in the DLR/A when compared to the
information stored in the DALI devices. This can, for example, be the case if exchanged or pre-programmed DALI devices
with a group assignment are installed on the DLR/A.
Telegram value
Function
Disable sending of fault alarm
0 = enabling of fault messages (lamp and ballast fault)
1 = disabling of fault messages (lamp and ballast fault)
Note
This function can, for example, be useful for systems with emergency lighting applications for daily checking
of the lamps of the DALI devices by the DALI control line, and thus disconnect them from the DALI master
(DLR/A). In this case, the DLR/A detects the loss of the DALI device and sends a ballast fault even though
this is a normal operating state. Should the fault message be disabled before separation from the DALI
control line, no fault is reported on the DLR/A. Operation can continue as normal. After checking the lighting
equipment, normal monitoring can be reactivated via the error message communication object Disable
sending of fault alarm.
Fault DALI
0 = There is no DALI conflict, i.e. the state (groups and scenes) matches the information stored in the
DLR/A.
1 = There is a DALI conflict
Object name
DALI output
DALI output
DLR/A 4.8.1.1 | 2CDC507128D0202 135
Data type
Flags
1 byte
C, W
DPT 1.003
1 bit
C, R, T
DPT 1.005

Advertisement

Table of Contents
loading

Table of Contents