3.3.8

Communication objects function Staircase lighting

Communication objects for the function Staircase lighting can be enabled in
Functions, page 82. A maximum of two communication objects can be enabled simultaneously for the
function Staircase lighting. The communication objects appear as number 37 or 38.
No.
37/38
This communication object can be enabled in
as one of the two additional communication objects,
This communication object is used for activation/deactivation of the function Staircase lighting. On deactivation, the lighting
group behaves like a "normal" lighting group of the DLR/A without function Staircase lighting. The function Staircase lighting
can be reactivated if a telegram with the value 1 is received on the DLR/A via this object.
By setting the T flag, the communication object is actively sent after KNX bus voltage recovery.
Telegram value:
As long as function Staircase lighting is activated, the staircase lighting is initiated by a telegram with the value 1 to one of
both communication objects Switch or Switch/status.
In
Parameter window - Gx Staircase
dimming or scene telegram interrupts the function Staircase lighting.
Furthermore, using this communication object, the status of function Staircase lighting can be provided on the KNX. The
status indicates whether the function Staircase lighting is activated or deactivated. It does not show that the Staircase lighting
is running.
For further information see:
37/38
This communication object can be enabled in
communication objects,
It serves when the function Staircase lighting is activated for permanent switch on of the lighting (also called "Service light").
The staircase lighting time is set to permanent. Thus, the staircase lighting remains on until a telegram with the value 0 is
received via the communication object Staircase lighting permanent ON.
After KNX bus voltage recovery or download, the value of the communication object is set to 0 and a permanent on is not
active.
Telegram value:
37/38
This communication object can be enabled in
communication objects,
The value of the communication object is used to provide a warning before the staircase lighting time times out. The
communication object has the value 1 during the warning.
Should the Time for dimming down after light on (Warning before light turned off) be parameterized with jump to, no warning
is parameterized for the staircase lighting. The communication object Warning staircase lighting remains unchanged with the
value 0 (no warning).
Should a forced operation be activated during the warning, the warning is reset, the communication object Warning staircase
lighting receives the value 0 and a telegram with the value 0 is sent on the KNX.
Function
Stairc. light. activate/status
0 = Staircase lighting is deactivated
1 = Staircase lighting is activated and started
lighting, page 90, you can parameterize whether a switch, brightness value, relative
Parameter window - Gx Staircase
Staircase light. permanent ON
0 = permanent ON not active
1 = Permanent ON active
Warning staircase lighting
Object name
Group 1
Parameter window - Gx
Functions, page Fehler! Textmarke nicht definiert.,
lighting, page 90, or
Group 1
Parameter window - Gx
Functions, page 82, as one of the two additional
Group 1
Parameter window - Gx
Functions, page 82, as one of the two additional
Parameter window - Gx
Data type
Flags
1 bit
C, R, W, T
DPT 1.003
Staircase
lighting, page 163
1 bit
C, R, W, T
DPT 1.003
1 bit
C, R, T
DPT 1.005
DLR/A 4.8.1.1 | 2CDC507128D0202 153