Communication Objects Scene X/Y - ABB i-bus KNX Product Manual

Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
3.3.5

Communication objects Scene x/y

The 8 bit scene communication object is always available. The communication objects for the 1 bit control
of a scene are only visible when the respective scene has been enabled in
page 113. Enable is always in pairs.
In
Parameter window Scene
Note
The function Staircase lighting is comprised of two scenes. The DLR/A automatically selects the internal
scenes 13 and 14 when the function Staircase lighting is selected.
For further information see:
No.
212
This communication object is always enabled.
Using this 8 bit communication object, a scene telegram can be sent using a coded telegram which integrates the lighting
groups in a KNX scene. The telegram contains the number of the respective scene as well as the information whether the
scene is to be retrieved, or if the brightness values in the scene are to be assigned to the lighting group in the scene.
Telegram value (1 Byte): M0SS SSSS
Other numeric values do not affect the communication objects Store scene or Recall scene.
For further information see:
146 2CDC507128D0202 | DLR/A 4.8.1.1
x, page 114, which lighting group is a member of the scene.
Staircase
lighting, page 163
Function
8 bit scene
(MSB) (LSB)
M: 0 = scene is recalled
1 = scene is stored (if allowed)
S: Number of the scene (1...13: 00000000...00001101)
KNX 8 bit telegram value
Decimal
00
01
02
...
13
128
129
130
...
141
Code table 8 bit scene (No.
Object name
Scene 1...14
Hexadecimal
00h
Recall scene 1
01h
Recall scene 2
02h
Recall scene 3
...
0Dh
Recall scene 14
80h
Store scene 1
81h
Store scene 2
82h
Store scene 3
...
8Dh
Store scene 14
212), page 206
Parameter window
Scenes,
Data type
Flags
1 byte
C, W
DPT 18.001
Meaning
...
...