Dali-light controller dlr/a 4.8.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
72 2CDC507128D0202 | DLR/A 4.8.1.1
Status of burn-in
Options:
no
yes: via object "Burn-in lamp/status"
The DLR/A features the option of sending the status of the function Burn-in on the KNX via
communication object Burn-in lamp/status.
no: No status message is sent for the function lamp burn-in.
yes: The communication object Burn-in lamp changes to Burn-in lamp/status. If this
communication object receives an ON telegram, the function Burn-in is started and the status
is sent on the KNX. The following parameter appears:
Send
Options:
after a change
after request
after a change or request
after a change: The status is sent via the communication object after a change.
after request: The status is sent after a request by the communication object Request
status values.
after a change or request: The status is sent via the KNX when the status changes or
the status is requested via the communication object Request status values.