Advertisement

ABB i-bus
KNX
Commissioning
With the option yes, the following parameters appear:
"Fault group/device code"
enable encoded fault message
Options:
With this parameter, the communication object 
Fault group/device code can be enabled. The fault status
(lamp and ballast fault) of the lighting groups or the individual DALI devices are sent on the KNX.
For further information see:
page 202
no: The communication object Fault group/device code is not enabled.
yes: The communication object Fault group/device code is enabled. The following parameter appears:
62 2CDC507128D0202 | DLR/A 4.8.1.1
Send
Options:
after a change
after request
after a change or request
after a change: The status is sent via the communication object after a change.
after request: The status is sent after a request by the communication object Request status
values.
after a change or request: The status is sent via the KNX when the status changes or the
status is requested via the communication object Request status values.
no
yes
Communication object No.
Send number of the failed group or
failed device
Options:
group orientated
based on DALI device
This parameter determines whether the fault relates to a lighting group or an individual DALI device.
group orientated: The values of the communication objects Fault group/device code (No. 19)
and No. Group/device fault (No. 21) relate to a lighting group fault. The numbers of the lighting
groups and information about the lighting groups are sent.
based on DALI device: The values of the communication objects Fault group/device code (No.
19) and No. Group/device fault (No. 21) relate to a DALI device fault. The numbers (DALI short
addresses with 1 added) of the DALI devices and information about the DALI devices are sent.
19, page 133, and
Code table Fault group/device code (No.
19),