ABB Switzerland Ltd
Boosting for NSD570/NSD70C in channel 2 is disabled
while NSD570/NSD70C in channel 1 is boosted or while
one or both NSD600 devices are boosted.
Boosting for NSD570/NSD70C in channel 3 is disabled while
NSD570/NSD70C in channel 1 or channel 2 or while one or both
NSD600 devices are boosted.
5.3.

Configuration with HMI600

In this section it is explained, how to create a configuration with the
HMI600 for a ETL600 equipment. It is recommended to work through
the next sections step by step. After this you will have created a
configuration, which you should store in a file. This is described in
section 5.4.
5.3.1.

Configure services

In the dialog box Connect, which appears after starting up HMI600 or
- if HMI600 is already running - after selecting File / New, choose Off
line. Close the dialog box by pressing Ok.
Point to Configuration / Services to get a dialog box with the tabs
Type, Data communication, APLC channel 1. Of these tabs, the tab
Type has to be configured first.
Note:
5.3.1.1.

Type

On the tab Type:
- Set the desired RF output power to 10, 20, 40 or 80 W PEP as
required. The setting 80 W requires two power amplifiers P1LA as
described in section 3.2.
- Choose the nominal bandwidth Bn [kHz] as required. Values of 4, 8,
12, 16, 20, 24, 28, 32 kHz are possible.
- Select the number of APLC channels. Depending on the nominal
bandwidth, at most 3 such channels are possible. Refer to Table
3-1, page 3-5 for the supported configurations.
The bandwidth of the DPLC channel in the rightmost field follows from
the nominal bandwidth and the number of APLC channels.
5.3.1.2.

Data communication

On the tab Data communication,
In the frame Data ports,
- select 1 V.11 / up to 2 V.24, if in slot N45 a P4LT board (without
piggyback module) is to be inserted;
5-14
1KHW001489-EN
Configuration data entered into the three tabs Type,
Data communication, APLC Channel 1, APLC
Channel 2 and Channel 3 of the dialog Configura-
tion / Services must be complete before proceeding
to the settings for these services.