Technical Data ETL600 Rel. 1
Broadband data (MOD600)
Application
Number of integrated broadband modems
Transmission bandwidth
Programmable data rates
Fallback / fall-forward
Multiplexer (MUX600)
Application
Number of channels
Multiplexing method
Number of V.24/RS-232 ports
Data rates
Number of V.11/X.24 ports
Data rates
TELEPROTECTION (NSD600)
Application
Number of units
Number of commands
Secure against
Bandwidth requirement
Guard signal
Processing of received signal
Number and type of inputs
Method of tripping
Voltage ranges
Number and type of outputs
Tripping voltage
Tripping current
HMI configurable
Event logging
Teleprotection performance
Performance criteria, description of measurement
Nominal transmission time (back-to-back operation,
including PLC equipment delay and operating times of
the teleprotection interface I/Os; noise free channel)
Security - probability of an unwanted command
(200 ms noise, 200 ms pause, worst case SNR)
Dependability - probability of missing a command
required channel condition
for actual transmission time
1)
Valid for the solid state command outputs, add 5...8 ms for the relay contact command outputs.
1KHW001498-EN
Transmission of high-speed / high capacity data in bandwidth of 4 kHz or higher.
1
4, 8, 12, 16, 20, 24, 28, 32 kHz
9.6, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64,
72, 76.8, 80, 96, 112, 128, 144, 153.6, 160, 192, 224, 256, 288, 307.2, 320 kbps
According to 5 user-selectable data-rates
Time-division multiplexing of a number of data channels into an aggregate data stream
8
TDM, with data flow control and speed adaptation according to aggregate capacity
2 or 6 (option); with optional port sharing and jabber timeout for point-multipoint operation
600, 1'200, 2'400, 4'800, 9'600 or 19'200 bps with MOD600
100, 200, 600, 1'200, 2'400, 4'800, 9'600 bps with NSK600
1 or 2 (option)
9.6, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64,
72, 76.8, 80, 96, 112, 128, 144, 153.6, 160, 192, 224, 256, 288, 307.2, 320 kbps
Transmission of protection commands for line- and objects protection
1 or 2 integrated NSD600
4 independent commands for each NSD600, simultaneously transmitted,
individually configurable for blocking, permissive or direct tripping,
plus 1 test command per NSD600
Noise (continuous or impulsive), speech and sweep tones,
DTMF (CCITT 48430 or ITU-T Q.23) in-band signaling
Nil; command signal transmission in-band (alternate purpose, with signal boosting)
ETL-pilot signal, or own guard signal above speech band 2000, 2200 or 2400 Hz
adaptive (to prevailing channel condition, always ensuring shortest transmission times)
4 optocoupler per Teleprotection Interface G4AI
Contact and battery, or dry contact
24 to 250 VDC, selectable in 4 ranges
4 solid state relays and 2 mechanical relay contacts per Teleprotection Interface G4AI
5 to 250 VDC nominal
≤ 1 A carry / 2 A peak solid state
5 A carry / 20 A peak mechanical relay
Command and alarm assignments to I/O ports
Command pick-up times, hold times, duration monitoring
State of command outputs during link alarm
Alarm and unblocking levels thresholds
2'600 time-stamped events, command counters; stored in non-volatile memory
Abbrev.
Blocking
1)
T0
≤ 10 ms
Puc
< 1E-04
Pmc
< 1E-03
SNR
< 6 dB / < 4 dB
1)
Tac
< 14 ms / < 15 ms
Edition 2005-11-11
ABB Switzerland Ltd
Permissive tripping
Direct tripping
≤ 11 ms
≤ 12 ms
< 1E-06
< 1E-09
< 1E-03
< 1E-04
< 6 dB / < 3 dB
< 6 dB / < 2 dB
< 16 ms / < 20 ms
< 20 ms / < 26 ms
3 / 4