Revision:
A
3
Changing from 230 VAC to 115 VAC
1) Unplug the module from the equipment
2) Unscrew the four bolts on top to remove the cover
3) Remove the wire bridge X14-X15 for 230 VAC
4) Remove the two fuses F1 and F3
5) Insert two wire bridges X13-X14 and X15-X16 for 115 VAC
6) Insert two new fuses F1 and F3: 4 A slow-blow (ABB part no. XN 400018P0022)
7) Close the module by adding the cover and fixing it with the four bolts
8) Mark the 115 VAC box on the right side of the module with a pen
4
Changing from 115 VAC to 230 VAC
1) Unplug the module from the equipment
2) Unscrew the four bolts on top to remove the cover
3) Remove the wire bridges X13-X14 and X15-X16 for 115 VAC
4) Remove the two fuses F1 and F3
5) Insert the wire bridge X14-X15 for 230 VAC
6) Insert two new fuses F1 and F3: 2 A slow-blow (ABB part no. XN 400018P0019)
7) Close the module by adding the cover and fixing it with the four bolts
8) Mark the 230 VAC box on the right side of the module with a pen