ABB ETL600 Instruction Manual

Digital power line carrier system
Table of Contents

Advertisement

ETL600
1KHW001489-EN
Edition November 2005
Digital Power Line Carrier System
p
Instruction Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB ETL600

  • Page 1 ETL600 1KHW001489-EN Edition November 2005 Digital Power Line Carrier System Instruction Manual...
  • Page 2 2005-09-30 Edition 2005-11-17 This instruction manual applies to the ETL600 Release 1.0 system. We reserve all rights to this document, even in the event that a patent is issued and a different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted.
  • Page 3 1. Introduction 2. Safety Instructions 3. Structure and Function 4. User Interface Program 5. Configuration and Set-up 6. Assembly and Installation 7. Commissioning 8. Operation and Maintenance 9. Troubleshooting 10. Storage, Decommissioning and Disposal 11. Options Annex...
  • Page 5: Table Of Contents

    1KHW001489-EN ABB Switzerland Ltd Contents INTRODUCTION................1-1 1.1. Using the manual ................1-1 1.2. Application of the ETL600 ...............1-1 1.3. Requirements to be met by the operator ........1-2 1.4. Requirements to be met by the service personnel .......1-2 1.5. Guarantee provisions ..............1-2 SAFETY INSTRUCTIONS ..............2-1...
  • Page 6 MUX600 DPLC Channel Multiplexer and V.24 Port Sharing ...3-49 3.5.3.1. DPLC Channel Multiplexer...............3-50 3.5.3.2. V.24 Port Sharing................3-51 3.5.4. Data Port Interfaces .................3-51 3.5.4.1. G.703 (not supported with ETL600 Release 1)........3-52 3.5.4.2. V.11....................3-52 3.5.4.3. V.24....................3-52 3.6. Internal Teleprotection ..............3-53 3.6.1. Introduction ..................3-53 3.6.2.
  • Page 7 ETL600 1KHW001489-EN ABB Switzerland Ltd 3.6.6. Performance criteria.................3-66 3.6.6.1. General ....................3-66 3.6.6.2. Transmission time ................3-66 3.6.6.2.1. Nominal transmission time (T0) ............3-67 3.6.6.2.2. Maximum actual transmission time (Tac).........3-68 3.6.6.3. Security ....................3-68 3.6.6.4. Dependability ...................3-69 3.6.7. Operating principle ................3-71 3.6.8. Functional description ..............3-72 3.6.8.1.
  • Page 8 Introduction ..................4-1 4.2. Installation ..................4-2 4.2.1. System requirements .................4-2 4.2.2. Install HMI600 ..................4-2 4.3. Using HMI600..................4-2 4.4. Communication to the ETL600 ............4-3 4.4.1. Specifying a Write password..............4-3 4.4.2. Direct connection via cable ..............4-3 4.4.2.1. Communication media ...............4-4 4.4.2.2. Communication settings..............4-4 4.4.2.3.
  • Page 9 ABB Switzerland Ltd 4.7. Data management ................4-14 4.8. Compatibility ..................4-15 4.8.1. ETL600 releases, release numbers, version numbers, type codes .4-15 4.8.2. Compatibility between modules of a PLC terminal......4-16 4.8.3. Compatibility between the two ETL600 terminals of a link....4-16 4.8.4. Compatibility of HMI600 to ETL600 terminals........4-16 4.8.5.
  • Page 10 1KHW001489-EN ETL600 ABB Switzerland Ltd 5.3. Configuration with HMI600............5-14 5.3.1. Configure services ................5-14 5.3.1.1. Type ....................5-14 5.3.1.2. Data communication ................5-14 5.3.1.3. APLC channels 1, 2 and 3 ...............5-15 5.3.1.4. Internal teleprotection...............5-15 5.3.2. Configure System................5-16 5.3.2.1. Equipment Settings ................5-16 5.3.3. Configure NSD600 ................5-16 5.3.4.
  • Page 11 8.3. Maintenance ..................8-6 8.3.1. Periodic functional checks..............8-6 8.3.1.1. Check input power supply voltage .............8-6 8.3.1.2. Check alarm status for ETL600 element management networks ..8-6 8.3.1.3. Check alarm events ................8-7 8.3.1.4. Check status data ................8-7 8.3.1.5. Check frequency response ..............8-7 8.3.1.6.
  • Page 12 1KHW001489-EN ETL600 ABB Switzerland Ltd 9.3.3. Grouping of alarms................9-6 9.3.4. Affected services................9-7 9.3.5. Affected hardware ................9-8 9.3.6. Alarm source ..................9-8 9.3.7. Alarm hierarchy ..................9-8 9.3.7.1. Top-level alarms/warnings ..............9-8 9.3.7.2. High-level alarms/warnings ..............9-8 9.3.7.3. Low-level alarms/warnings..............9-9 9.3.7.4. Detail alarms/warnings...............9-9 9.3.8. Alarm outputs ..................9-9 9.3.8.1.
  • Page 13 ETL600 1KHW001489-EN ABB Switzerland Ltd 9.6.3.6. G4AI detail interface alarms.............9-28 9.6.3.7. G4AI detail warnings ................9-29 9.6.4. TDM Bus communication alarms and warnings.......9-29 9.7. Replacement of faulty items ............9-29 9.8. Dispatch for repairs ...............9-30 9.9. Support ...................9-30 STORAGE, DECOMMISSIONING AND DISPOSAL ......10-1 10.1.
  • Page 14 1KHW001489-EN ETL600 ABB Switzerland Ltd List of Figures Fig. 3-1 ETL600 with a wide range of services........3-2 Fig. 3-2 Adjacent (a) and non-adjacent (b) frequency bands ..3-2 Fig. 3-3 Use of nominal frequency band for pure APLC (a), pure DPLC (b) or mixed APLC/DPLC (c) operation in ETL600 erect mode ............3-4...
  • Page 15 Duplicated protection for a single-circuit line....3-64 Fig. 3-40 Examples for allocation of the 4 kHz band with speech and the ETL600 pilot as NSD600 guard signal .....3-74 Fig. 3-41 Examples for allocation of the 4 kHz band with speech and an own NSD600 guard signal.........3-74 Fig.
  • Page 16 1KHW001489-EN ETL600 ABB Switzerland Ltd Fig. 6-6 Side plate of power subrack P7LA with supply connections ..............6-10 Fig. 6-7 The plate A9CS for connection of external RF coaxial cable ................6-10 Fig. 6-8 The terminal block for connection of power supply ..6-11 Fig.
  • Page 17 ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 9-2 Alarm processing – block diagram ........9-6 Fig. 9-3 Grouping of alarms.............9-7 Fig. 9-4 Derivation of high-level alarms ...........9-9 Contents November 2005 XIII...
  • Page 18 Table 6-1 List of cables with wire sizes for connector blocks ..6-15 Table 9-1 Fuses in the equipment ...........9-4 Table 9-2 Fault location of an ETL600 link ........9-5 Table 9-3 The six LEDs on the frontplate of P4LT......9-10 Table 11-1 Available license keys ...........11-4...
  • Page 19 Logarithmic unit for relative levels Direct Current Data Circuit-terminating Equipment Direct Digital Synthesis DPLC Digital Power Line Carrier Digital Signal Processor Data Terminal Equipment Signaling wire from PAX E40A Type of cabinet E5TX ETL600 Tx filter Electromagnetic Compatibility Contents November 2005...
  • Page 20 Low Frequency Loss Of Signal Signaling Wire to PAX MC / uC Micro Controller MOD600 ETL600 Modem in the DPLC channel MUX600 ETL600 Data Terminal Multiplexer N.A. / n.a. Not Applicable or Not Available Normally Closed (terminal of switchover relays)
  • Page 21 ABB Switzerland Ltd OFDM Orthogonal Frequency Division Multiplex P1LA Power Amplifier 40 W P1LX Interface Extension board (piggyback for P4LT) P3LE ETL600 RF Hybrid P3LK Dummy Load 80 W P3LG ETL600 Carrier Combiner P3LL Transmit filter tuning adapter P4LM Receive filter tuning adapter...
  • Page 22 1KHW001489-EN ETL600 ABB Switzerland Ltd Send Data Synchronous Digital Hierarchy Surface Mounted Device Signal to Noise Ratio SONET Synchronous Optical Network Send Timing Shielded Twisted Pairs Time Division Multiplex Transmission Control Protocol Teleprotection Equipment Terminal Timing Transmit(ter) UART Universal Asynchronous Receiver Transmitter Unshielded Twisted Pairs V.11...
  • Page 23: Introduction

    ETL640 and ETL680 are the members of the ETL600 family. They are assembled in standard 19” racks, one with 6 ASA-units carrying the signal processing modules and one or two with 3 ASA-units housing the 40 W power amplifier and associated modules.
  • Page 24: Requirements To Be Met By The Operator

    1KHW001489-EN ETL600 ABB Switzerland Ltd sub-stations. The communication services supported by the ETL600 are: • Telephony, • Data, • Teleoperation, • Teleprotection or combinations thereof as explained in chapter 3. 1.3. Requirements to be met by the operator • The operator must have a general understanding of electronic and electrical systems.
  • Page 25: Safety Instructions

    SAFETY INSTRUCTIONS 2.1. Safety information The ETL600 equipment itself is safe and without any risk. This is not valid for its containment and the peripheral surrounding, like the high voltage area and lines. Only service personnel is therefore allowed to execute all the steps and manipulations described in this manual.
  • Page 26: Basic Principles

    1KHW001489-EN ETL600 ABB Switzerland Ltd 2.2. Basic principles The ETL equipment complies with the latest standards of engineering and the recognized safety regulations. In spite of this, hazards could arise with inappropriate operation of the equipment. The ETL equipment should only be operated in fault free condition and within the guidelines lay down in the instruction manual.
  • Page 27 PCB Extenders For measuring purposes only the original PCB DANGER extenders P4LM, P3LL and I9BK, designed to work with ETL600 equipment, must be used. ESD protection The modules in this equipment contain devices, Caution which can be damaged by electrostatic discharges.
  • Page 28 1KHW001489-EN ETL600 ABB Switzerland Ltd Electrical Installation This is a Class Ι equipment as specified in DANGER IEC60950. The equipment and the cabinet must be earthed. The equipment must be supplied over the “circuit breaker for the power supply“, type B9AS.
  • Page 29 Appropriate measures have to be taken especially in case protecti on signal transmission is being used. During routine tests with the ETL600 in operation Caution the "Reset" item in the Equipment menu of the HMI600 should not be activated, as this causes the equipment to be re-initialized and thus be blocked for some seconds.
  • Page 30 1KHW001489-EN ETL600 ABB Switzerland Ltd P1LA Hazardous voltages and/or hazardous energy level DANGER at the heat sink. Do not touch during operation. Heat sink should not be touched with conducting DANGER materials to avoid energy discharges and damage of the power amplifier.
  • Page 31 ETL600 1KHW001489-EN ABB Switzerland Ltd O4LE The phone interface on the module O4LE generates DANGER dangerous voltage up to 100 V. Don’t use the module without upper and lower cover plate. Do not touch the open pins of the service phone connector, the leads of its cable, the pins of the external ca connector and the leads of the external cable.
  • Page 33: Structure And Function

    ETL600 1KHW001489-EN ABB Switzerland Ltd STRUCTURE AND FUNCTION 3.1. Introduction Transmission lines exhibit low attenuation in the carrier frequency range between 20 and 500 kHz. They are therefore a good means of communicating information over medium to long distances (20 to 100 km, or 100 to 500 km respectively).
  • Page 34 1KHW001489-EN ETL600 ABB Switzerland Ltd However, the bands can also be separated in frequency as shown in Fig. 3-2b. ETL600 offers nominal bandwidths from 4 to 32 kHz. Protection commands Protection commands V.24, 4-w 600 Ohm AF V.24, 4-w 600 Ohm AF...
  • Page 35: Aplc And Dplc Services

    The standard high frequency power output of the basic ETL600 unit is 40 W. This is for most cases adequate to ensure the required transmission quality. For severe operating conditions with high attenuation or high noise levels - e.g.
  • Page 36: Dplc (B) Or Mixed Aplc/Dplc (C) Operation In Etl600 Erect Mode

    By default, the APLC band is located below the DPLC band on the frequency scale as shown in Fig. 3-3c. This placement is referred to as erect ETL600 overall mode. It is possible to operate the link in inverted overall mode if desired, with the effect that the signal spectra of Fig.
  • Page 37 B , while in inverted mode, f is the higher edge frequency. Table 3-1 lists all possible settings. Spectrum ETL600 overall mode = Erect ETL600 overall mode = Inverted APLC APLC (NSD600#1) (NSD600#1)
  • Page 38: Fig. 3-4 Use Of Nominal Frequency Band For Pure Aplc (A), Pure

    NSD600 device. In most cases, even two such devices can be used. In all modes of operation, ETL600 complies to IEC publication 60495 “Single sideband power-line carrier terminals”. Wherever this standard isn’t directly applicable for DPLC, the requirements have been suitably...
  • Page 39: Frequency Allocation In Af Channels

    ETL600 1KHW001489-EN ABB Switzerland Ltd 3.1.2. Frequency allocation in AF channels The frequency allocation of an AF channel is typically as depicted in Fig. 3-5. The pilot band, typically at the upper end of the AF frequency band, must be kept free because it is used by the PLC equipment for an auxiliary signal called 'pilot'.
  • Page 40: Fig. 3-6 Use Of Etl Bandwidth For A 4 Khz Af Channel

    1KHW001489-EN ETL600 ABB Switzerland Ltd ETL600: Usable bandwidth of a 4kHz AF channel Speech 2000 Hz Speech 2200 Hz Speech 2400 Hz Standard Speech 2600 Hz Pilot Speech 2800 Hz 3840 Hz Speech 3000 Hz Speech 3200 Hz Speech 3400 Hz...
  • Page 41: Fig. 3-7 Use Of Etl Bandwidth For A 3.2 Khz Af Channel

    ETL600 1KHW001489-EN ABB Switzerland Ltd ETL600: Usable bandwidth of a 3.2kHz AF channel Speech 2000 Hz Speech 2200 Hz Standard Speech 2400 Hz Pilot Speech 2600 Hz 3120 Hz Speech 2800 Hz Standard NSD600 own 2240 NSD600 2440 Guard guard options...
  • Page 42: Fig. 3-8 Use Of Etl Bandwidth For A 2.4 Khz Af Channel

    1KHW001489-EN ETL600 ABB Switzerland Ltd ETL600: Usable bandwidth of a 2.4kHz AF channel Standard Speech 2000 Hz Pilot 2280 Hz 50 Bd/120Hz (R.35) Not available in ETL600 Rel.1 100 Bd/240 Hz 1200 1440 1680 1920 (R.37) 200 Bd/360 Hz 1260...
  • Page 43: System Architecture

    ABB Switzerland Ltd 3.2. System architecture ETL600 may be tailored to the specific needs of the application thanks to its modular architecture. The modules are housed in one, two or three standard 19" subracks, mounted on top of each other as shown in Fig.
  • Page 44: Fig. 3-9 Etl640/680 Configurations

    1KHW001489-EN ETL600 ABB Switzerland Ltd Fig. 3-9 ETL640/680 configurations Slot types for channel subrack 7 (P7LC), Fig. 3-9: Basic equipment : Optional RF equipment (depending on desired RF-frequencies and -power) : Optional LF equipment (depending on desired services) Interface boards 1 (O4LE) and 2 (G4AI) are required to support the APLC services telephony, teleoperation and teleprotection.
  • Page 45 ETL600 1KHW001489-EN ABB Switzerland Ltd Supply P7LC Telephony TDM bus Teleoperation P7LA B5LA B4LE O4LE B5LC Ext. teleprotection P4LU (e.g. NSD570) P1LA Teleprotection G4AI (optional) E5TX IRIG-B Data V.11, V.24 P4LT Data V.11, V.24 P3LE Coax (optional) P1LX cable Alarm contacts...
  • Page 46 1KHW001489-EN ETL600 ABB Switzerland Ltd Supply P7LC Telephony TDM bus P7LA Teleoperation B5LA B4LE B5LC O4LE Ext. teleprotection P4LU (e.g. NSD570) P1LA Teleprotection G4AI (optional) IRIG-B Data V.11, V.24 P4LT Data V.11, V.24 P3LE E5TX Coax cable (optional) P1LX Alarm contacts...
  • Page 47: Fig. 3-12 Functional Block Diagram Etl680

    ETL600 1KHW001489-EN ABB Switzerland Ltd Supply Supply P7LC Lower Upper rack rack P7LA P7LA Telephony TDM bus Teleoperation B5LA B5LC O4LE B4LE B5LA B5LC Ext. teleprotection P4LU (e.g. NSD570) P1LA Teleprotection P1LA G4AI (optional) E5TX IRIG-B E5TX Data V.11, V.24...
  • Page 48: Digital Signal Processing

    The reverse procedure was employed for recovering the LF signal. It required critical analog filters for achieving the desired filter characteristics. However, in ETL600, the AF signal is first converted into a digital signal (a serial sequence of codewords consisting of Zeros an Ones) by an analog to digital converter.
  • Page 49 ® the equipment, the user interface program HMI600 - a Windows application - is needed, which is an integrated part of ETL600. Access via dial-up modems and the intranet/internet is also supported by the HMI600 program. For internet access, the server program SVR600, available as an option, is required in addition to the HMI600.
  • Page 50: Module Description

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.3. Module description 3.3.1. AF interface O4LE The AF interface board O4LE is a universal interface for audio frequency signals. It supports the applications: • Telephony, • Teleoperation, • External teleprotection. These are the analog services described in section 3.4.
  • Page 51: Frontplate

    ETL600 1KHW001489-EN ABB Switzerland Ltd 3.3.1.1. Frontplate 'AL' LED red: Module hardware alarm This LED is on, if a hardware alarm on the module is detected. 'RDY' LED green: Module ready On as long as the module is in normal operation mode.
  • Page 52: Teleprotection Interface G4Ai

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.3.2. Teleprotection interface G4AI 3.3.2.1. Summary The teleprotection interface includes: • four input circuits equipped with optocouplers, • four output circuits equipped with semiconductors (referred to as 'solid state outputs'), • two electro-mechanical output relays with change-over contacts (referred to as 'relay outputs').
  • Page 53: Relay Outputs

    ETL600 1KHW001489-EN ABB Switzerland Ltd external contact. The protection relay should provide potential–free contacts for this purpose. The input circuits are current limited, no external precautions have to be taken. Each input can be programmed with the help of the user interface HMI600 for one of the many foreseen functions, e.g.:...
  • Page 54: Frontplate

    1KHW001489-EN ETL600 ABB Switzerland Ltd Although the relay contacts are of the 'heavy-duty' type, external precautions have to be taken for limiting the circuit current. 3.3.2.5. Frontplate 'AL' LED red: Module hardware alarm On if a hardware alarm on the module is detected.
  • Page 55: Rf-Converter P4Lt

    ETL600 1KHW001489-EN ABB Switzerland Ltd 3.3.3. RF-Converter P4LT The module P4LT is the heart of the ETL600 equipment. It performs the following main functions: • Conversion of the signals from LF (Low Frequency) to RF (Radio Frequency) • DPLC modem MOD600 •...
  • Page 56: Frontplate P4Lt

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.3.3.1. Frontplate P4LT 'RDY' LED red: System ready Lights if the ETL600 system is in normal P4LT operation. 'P4LT' LED red: Module hardware alarm Lights if a hardware alarm on P4LT is detected. 'SYS' LED red: Cabinet alarm / System alarm Lights if a system alarm is present.
  • Page 57: Rf-Converter P4Lu

    The RF-converter P4LU is identical to the RF-converter P4LT, except that it offers more ports: Ports P4LU P4LT V.24 V.11 G.703 The remaining ports are identical on P4LU and P4LT. Remark: 1) The G.703 and LAN ports are not supported with ETL600 Rel.1 Structure and Function November 2005 3-25...
  • Page 58: Frontplate P4Lu

    ETL600 ABB Switzerland Ltd 3.3.4.1. Frontplate P4LU 'RDY' LED green: System ready P4LU Lights if the ETL600 system is in normal operation. 'P4LU' LED red: Module hardware alarm Lights if a hardware alarm on P4LU is detected. 'SYS' LED red: Cabinet alarm / System alarm Lights if a system alarm is present.
  • Page 59: Alarm Relay Module R1Bc

    Alarm relay module R1BC The alarm relay module type R1BC is mounted on the back of the backplane P1LC of the ETL600 channel tier P7LC. 8 power relays are mounted on the alarm relay module. Each of the relays can be programmed by jumpers on R1BC individually to one of three alarm sources: User alarms 1, 2 or 3.
  • Page 60 1KHW001489-EN ETL600 ABB Switzerland Ltd User alarm 2 From P4LT User alarm 3 User alarm 1 R1BC CA-1 CA-5 R1-5 R1-1 R2-5 R2-1 NO NC 250V 250V 150W 150W 2000VA 2000VA CA-2 CA-6 R1-6 R1-2 R2-6 R2-2 NO NC 250V...
  • Page 61: Dc-Dc Converter B4Le

    ETL600 1KHW001489-EN ABB Switzerland Ltd 3.3.6. DC-DC converter B4LE The DC-DC converter type B4LE is used for converting the 48 V DC into ±12 V DC and +5 V DC voltages which are required by the modules of the channel rack. These voltages are internal to the equipment and not available externally.
  • Page 62: Transmit Filter E5Tx

    1KHW001489-EN ETL600 ABB Switzerland Ltd Us +38V to 45V X110 42V to 58V X107 to X183 X182 +26V B/D/Z16 HYB-IN B/D/Z14 X184 B/D/Z28 ZFFILT-IN TXRF12-A B/D/Z26 ZFFILT-GND TXRF12-B B/D/Z30 PAMPOUT-A TXRF34-A nom. 50W 20 Ohm B/D/Z32 Imax BIAS TXRF34-B PAMPOUT-B 0 ...
  • Page 63: Carrier Combiner P3Lg

    ETL600 1KHW001489-EN ABB Switzerland Ltd ...Cs1 ...Cs2 Amplifier Comb. / Hybr. Comb. / Hybr. Power Line ...Cp ...Cp (impedance matching) (impedance matching) Fig. 3-19 E5TX block diagram 3.3.10. Carrier combiner P3LG The carrier combiner P3LG is used only in case of the 80 W terminal ETL680.
  • Page 64: Rf Hybrids P3Le, Dummy Load P3Lk

    1KHW001489-EN ETL600 ABB Switzerland Ltd +12.8V Regulator TX filter 1 d/b/z16 7.33 select R 80W to hybrid resistors on 15.67 d/b/z24 heat sink 26.67 T202 d/b/z14 plug-out TXRF-40W TX filter 2 d/b/z22 TX Alarm Amplifier 2 d/b/z30 relay shown not energized...
  • Page 65 ETL600 1KHW001489-EN ABB Switzerland Ltd 125 Ohm TX Filter T3A1 line output d/b/z16 T3A2 75 Ohm to coax T3A3 d/b/z20 T3B1 operating mode 45 Ohm hybrid T3B2 transformer selective T3B3 supervision d/b/z14 RX RF signal RX level plug out R125...
  • Page 66 The transmitter frequency band is automatically converted to the receiver frequency band when the dummy load is inserted. Also, the equalizer in the Rx signal path of the ETL600 is bypassed. 3-34 November 2005...
  • Page 67: Receive Filter P4Rx

    ETL600 1KHW001489-EN ABB Switzerland Ltd 3.3.12. Receive Filter P4RX The receive filter is primarily used for the suppression of local and parallel transmitter signals. It is plugged in the rightmost slot of the channel rack P7LC. When it is unplugged, the filter input pins are automatically connected to the filter output pins on the backplane of P7LC.
  • Page 68: Power Supplies B5La And B5Lc

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.3.13. Power supplies B5LA and B5LC The power supply B5LA is used when the external power supply voltage is 48 VDC and the power supply B5LC is used when the external power supply is 230 VAC or 115 VAC. The power supply also...
  • Page 69: Fig. 3-25 Block Diagram Of P7La Equipped With B5La, E5Tx, P1La, P3Le

    ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 3-25 Block diagram of P7LA equipped with B5LA, E5TX, P1LA, P3LE Structure and Function November 2005 3-37...
  • Page 70: Analog Services

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.4. Analog Services The analog services comprise the following applications: Telephony • Point-to-point hot line (direct phone), • Remote subscriber, • 4-wire PAX connection with E&M signaling, • 2/4-wire PAX connection with E&M signaling and hybrid control, •...
  • Page 71: Remote Subscriber

    ETL600 1KHW001489-EN ABB Switzerland Ltd and output speech levels and ringer frequency are programmable. In order to improve the signal to noise ratio by up to 10 dB on noisy links, a compander function can be enabled. As long as the hot line is idle (both phones on hook), the service phone may utilize the speech channel.
  • Page 72: 4-Wire Pax Connection With E&M Signalling

    Local/Transit can be inverted independently. All signaling wires are galvanically isolated. The PAX only needs a dry relay contact to control M-Wire and Local/Transit input, since ETL600 provides an extra voltage source for these inputs. As long as the trunk line is idle, the service phone may utilize the speech channel.
  • Page 73: E&M Signaling

    ETL600 1KHW001489-EN ABB Switzerland Ltd when one compression and one expansion process takes place, the compander is only employed in the 2-wire local subscriber stations but not in the 4-wire transit stations. 3.4.1.5. E&M signaling For some applications, the AF signal of a first ETL-link has to be forwarded to a second link via teleoperation ports –...
  • Page 74: Teleoperation

    1KHW001489-EN ETL600 ABB Switzerland Ltd Remote Equipment Local Equipment Conversation Digit "1" Digit "2" ReleaseReq E-Wire M-Wire ReleaseAck M-Wire E-Wire RDY-LED RDY-LED OP-Phone OP-Phone RDY-LED RDY-LED Fig. 3-32 State of LEDs corresponding to internal E&M By watching the LEDs, it is easy to see whether a remote PAX is working or not.
  • Page 75: Transit Filters

    ETL600 1KHW001489-EN ABB Switzerland Ltd signal interruptions (typically less than 100 ms) caused by teleprotection command transmission in mode 'disconnectable' cannot be tolerated. As a consequence, the available power for teleprotection command signals is reduced accordingly. For more information on the management of signal levels for teleprotection, refer to section 3.4.3 ‘External teleprotection' and to...
  • Page 76: External Teleprotection

    ETL600. On the output side, a similar programmable attenuator/amplifier restores the signal strength to the level required at the output port.
  • Page 77: Data Communication

    3.5. Data Communication ETL600 offers a variety of options for data communication: two different types of modems for transmission over the PLC link and a range of physical interfaces to be used with various transmission formats.
  • Page 78: Data Regeneration With Fsk Modems

    1KHW001489-EN ETL600 ABB Switzerland Ltd • Datarates: ≤ 100, ≤ 200, ≤ 300, ≤ 600 and ≤ 1’200 bps with FSK; 2’400, 4’800 and 9’600 bps with DAPSK. The FSK modems with datarates of ≤ 200 and ≤ 1’200 bps are available in two versions with different bandwidths.
  • Page 79: Required Data Transmission Format Parameter For Dapsk

    ETL600 1KHW001489-EN ABB Switzerland Ltd • the non-flat frequency response of the transmission channel, • noise and non-linear distortion on the transmission channel, • implementation losses of the modems. When the data signal satisfies certain conditions, isochronous distortion can be reduced using nonlinear processing. This is called regeneration.
  • Page 80: Table 3-3 Max. Mod600 Datarates

    1KHW001489-EN ETL600 ABB Switzerland Ltd 9.6, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64, 72, 76.8, 80, 96, 112, 128, 144, 153.6, 160, 192, 224, 256, 288, 307.2, 320 kbps, the upper limit being restricted by the choice of the DPLC bandwidth, refer to Table 3-3.
  • Page 81: Mux600 Dplc Channel Multiplexer And V.24 Port Sharing

    MOD600. This allows to spend more power to the frequencies not impaired by narrowband interferers. ABB has filed a patent for this method. The signal converter is equipped with one interface which can be routed directly to V.11 port 1 or to the DPLC channel multiplexer of...
  • Page 82: Dplc Channel Multiplexer

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.5.3.1. DPLC Channel Multiplexer The multiplexer combines up to 9 individual channels into a single aggregate channel. The data transfer rate, interface and data transfer format (synchronous, asynchronous, anisochronous) can be set individually for each of the individual channels. The aggregate channel is transmitted trough the MOD600 modem.
  • Page 83: V.24 Port Sharing

    External data terminals can be connected to the channels as follows: • One G.703 interface (not supported with ETL600 Release 1) synchronous data transfer at 64 kbps; • Up to two V.11 interfaces for synchronous data transfer at data transfer rates from 9600 up to maximum available datarate for MOD600;...
  • Page 84: G.703 (Not Supported With Etl600 Release 1)

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.5.4.1. G.703 (not supported with ETL600 Release 1) One interface according to ITU-T G.703 Standard § 4.2.1 is available on P4LU. This interface is limited to 64 kbps co-directional application for transmission with DPLC channel multiplexer.
  • Page 85: Introduction

    • SCADA applications using telegram based protocols for communication between master and RTUs: • ABB proprietary protocol RP570/RP571 based on IEC60870-1- 5 FT1.2 with 8 data bits, 1 stop bit and even parity; • ABB proprietary implementation of asynchronous DNP3.0 based on IEC60870-1-5 FT3 with 8 data bits, 1 stop bit and no parity.
  • Page 86: Intended Use Of Nsd600

    HMI600 for the ETL600 system. For the same reason commissioning, testing and maintenance also becomes easy. The use of the NSD600 in conjunction with ETL600 and HMI600 is documented and explained in this chapter. 3.6.2.
  • Page 87: Structure Of Nsd600

    The NSD600 signals are processed completely digitally by a DSP (Digital Signal Processor) on the RF-Converter type P4LT of the basic ETL600 equipment and by a DSP on the Teleprotection Interface type G4AI, so the firmware for the NSD600 resides on both modules.
  • Page 88: Features

    G4AI is inserted into the rack type P7LC of the ETL600 PLC equipment. Two individual NSD600 teleprotection equipment are configurable in the APLC and DPLC channels of the ETL600 system. • Advanced technology, digital signal processing High equipment availability and reliability due to carefully selected components which have passed rigorous qualification tests.
  • Page 89 ETL600 1KHW001489-EN ABB Switzerland Ltd • Signal boosting By switching off speech and data communication for a short time, the best use is made of the available transmitter power to guarantee reliable transmission of every tripping signal sequence. • Two tripping criteria Incorrect operation due to a single fault is prevented by processing guard and active signals separately.
  • Page 90: Applications

    Element Management Networks An embedded operation channel (EOC) allows remote NSD600 configuration and monitoring from one end. When the ETL600 equipment is integrated in a network management system, each NSD600 can be accessed with HMI600 via a unique equipment identification number.
  • Page 91: Permissive Tripping Schemes

    ETL600 1KHW001489-EN ABB Switzerland Ltd on the interface module are programmable; if a command requires two output contacts, for example, both outputs can be assigned to one interface or even to different interfaces. More inputs / outputs are easily achieved by inserting additional relay interfaces.
  • Page 92: Blocking Schemes

    1KHW001489-EN ETL600 ABB Switzerland Ltd or human error will cause unwanted, usually three-phase tripping of the line and will block the operation of any auto-reclosure relay. A genuine transfer tripping signal, on the other hand, must on no account be lost whether there is interference on the communications channel or not, because then a line fault would not be isolated with correspondingly serious consequences.
  • Page 93: Unblocking

    ETL600 1KHW001489-EN ABB Switzerland Ltd and reverse-looking directional units. A through-fault is seen by the directional unit which sends a signal to block the distance relay on the healthy line behind it. For a fault on the line, the reverse-looking directional units at the two ends do not send blocking signals and the overreaching first zones trip their respective circuit-breakers.
  • Page 94: Protecting Dual-Circuit Lines

    1KHW001489-EN ETL600 ABB Switzerland Ltd tripping signals. This 'emergency' feature can be used in different ways: • to switch the reach of the distance relay (under/overreaching first zone) • as an enabling signal by connecting the unblocking output contact in parallel with the tripping signal output of the NSD600. This is used above all in the case of permissive overreaching blocking schemes.
  • Page 95: Protecting Single-Circuit Lines

    ETL600 1KHW001489-EN ABB Switzerland Ltd LINE 1 B PHASE ETL600 MP1 Line 1 CF 1 MP2 Line 2 BFP Line 1 BFP Line 2 D NSD600 ETL600 MP1 Line 2 CF 2 MP2 Line 1 NSD600 LINE 2 MP1: 1st main protection...
  • Page 96 Important single-circuit lines (400 kV to 800 kV) are always equipped with duplicated main protection, breaker failure protection and perhaps a generator shutdown / load shedding facility. Two ETL600 links, each with a four-command NSD600, are then arranged in a fully duplicated teleprotection scheme according to Fig.
  • Page 97: Phase Segregated Line Protection

    Therefore the maximum boost level has to be carefully calculated (adapted to the ETL600 link for the second line section). No teleprotection interfaces may be inserted into the PLC equipment in...
  • Page 98: Performance Criteria

    1KHW001489-EN ETL600 ABB Switzerland Ltd much higher dependability when the channel is disturbed (which is usually the case while commands have to be transferred). 3.6.6. Performance criteria 3.6.6.1. General A fundamental requirement in all the applications that teleprotection equipment is used in, is that command signals are communicated reliably at the highest possible speed (transmission time).
  • Page 99: Nominal Transmission Time (T0)

    It is measured with nominal signal levels at the transmitter output and the receiver input. The ETL600 RF terminals are connected back-to-back via an artificial line with nominal attenuation.
  • Page 100: Maximum Actual Transmission Time (Tac)

    SNR. It is measured with continuous white noise applied to the RF input of the ETL600 receiver. Commands which are not received within a certain Tac are considered as lost or missed commands (refer also to section 3.6.6.4...
  • Page 101: Dependability

    ETL600 1KHW001489-EN ABB Switzerland Ltd All security measurements were performed according to the procedures prescribed in IEC 60834-1. Noise/bit error burst 200 ms Duration of pause 200 ms Noise bandwidth 4 kHz 0 dB … -30 dB Security is determined by coupling bursts of white noise of high amplitude into the communications channel.
  • Page 102 1KHW001489-EN ETL600 ABB Switzerland Ltd = (N ) / N = probability of missing a command = number of commands transmitted = number of commands received 3-70 November 2005 Structure and Function...
  • Page 103: Operating Principle

    ABB Switzerland Ltd 3.6.7. Operating principle The NSD600 uses the pilot signal of the ETL600 as a guard signal. It is continuously evaluated on the receive side. In case of insufficient signal quality (signal-to-noise ratio or signal level) the NSD600 initiates an alarm.
  • Page 104: Functional Description

    The NSD600 can be operated in one or two 4 kHz APLC channels of the ETL600 as well as in the first channel of the “three APLC in 8 kHz” mode. In case of a dual-channel ETL600 with one APLC and one DPLC, an NSD600 can also be operated in the DPLC.
  • Page 105: Speech Bandwidth

    Speech bandwidth The NSD600 supports all programmable speech channels (2.0, 2.2, 2.4, 2.6, 2.8, 3.0, 3.2 and 3.4 kHz) when using the ETL600 pilot as a guard signal. The trip frequencies are always transmitted in the band 0.3 … 2.0 kHz. Adequate filtering is performed to separate the band from superimposed teleoperation channels.
  • Page 106: Command Signals

    NSD600 Guardfilter 3840 Hz 2120 Hz 2520 Hz Fig. 3-40 Examples for allocation of the 4 kHz band with speech and the ETL600 pilot as NSD600 guard signal ETL: useful AF bandwidth Speech 2000 Hz Teleoperation Ch. Guard Pilot Speech 2200 Hz Teleop.
  • Page 107: Trip Frequencies

    ETL600 1KHW001489-EN ABB Switzerland Ltd command. Transmitting two discrete frequencies gives added security against speech and interference, e.g. an audio frequency generator. Compared to single tone command signals, the multiplex dual tone command signal has the same amplitude (peak envelope power), but 3 dB lower rms power since each tone is transmitted at a 6 dB lower voltage level.
  • Page 108: Command Assignment To Trip Frequencies

    This in turn is dependent on just how many signals the ETL600 has to handle and for this reason, the boost ratio is calculated automatically by the HMI600 after configuring the equipment.
  • Page 109: Input/Output Command Handling

    ETL600 1KHW001489-EN ABB Switzerland Ltd It may be necessary to select some teleoperation channels to be 'not disconnectable' later, the boost ratio is accordingly decreased then by the HMI600 (a corresponding warning note will appear on the screen). Since both TPE interrupt the DPLC channel and all disconnectable...
  • Page 110: Tx Input Command Delay

    1KHW001489-EN ETL600 ABB Switzerland Ltd Local Command at G4AI Input Local Command e.g. 5 ms with Tx Input Delay Local Command with Tx Input e.g. 20 ms Prolongation T0, e.g. 10 ms Remote Command as received of TPE (DSP on P4LT)
  • Page 111: Tx Trip Duration Monitoring

    ETL600 1KHW001489-EN ABB Switzerland Ltd 3.6.8.6.4. Tx Trip Duration Monitoring The duration of each single command injected at the relay interface inputs is separately and continuously monitored. Alarm is given and the guard signal is transmitted instead of the tripping signal should the command duration exceed a predefined value (5 seconds per default, programmable via HMI600 in the range of 1 to 60 seconds).
  • Page 112: Start Inputs

    1KHW001489-EN ETL600 ABB Switzerland Ltd Alarm is given and the command output is set inactive should the command duration exceed a predefined value (if monitoring is enabled: 5 seconds per default, programmable via HMI600 in the range of 1 to 60 seconds).
  • Page 113: Command Outputs During Link Failure

    ETL600 1KHW001489-EN ABB Switzerland Ltd unblocking signal is only released if both levels are below the threshold and the other conditions mentioned above are fulfilled too). 3.6.8.9. Command Outputs During Link Failure By means of the HMI600, the user can program how the command outputs respond to a channel failure, i.
  • Page 114: Tx Command Acknowledge

    P4LT to one of the various outputs on the teleprotection interface type G4AI (configurable by means of the HMI600). Reception of the ETL600 pilot signal (when used as guard signal) or the own NSD600 guard with adequate signal quality means that the corresponding solid state output is closed or the coil of the selected relay contact is energized.
  • Page 115 The loss of the guard signal is, however, signaled by both ETL600 and NSD600. The testing facilities impair in no way the ability of the equipment to respond to a protection command, i.e.
  • Page 116: Manual Loop Test

    1KHW001489-EN ETL600 ABB Switzerland Ltd The signal used for this test has the same parameters as the command with the highest application requirements regarding security. 3.6.8.14. Manual Loop Test The loop test can also be initiated manually from any station via the HMI600.
  • Page 117: Alarms Sources

    A list of alarm messages and their causes can be found in section 9.6. The alarm concept of the ETL600 including NSD600 is described in section 9.3.1. The following criteria are continuously monitored and produce alarms (the list is not final): •...
  • Page 118: Alarm / Warning Contacts

    1KHW001489-EN ETL600 ABB Switzerland Ltd 3.6.8.18. Alarm / Warning Contacts Following NSD600 alarms can be signaled individually per TPE on any output of G4AI (it is noted that the alarm signals of only one TPE can be signaled on the same G4AI – as it applies for the command signals too): •...
  • Page 119: Interference In Speech Band

    3.7.1. General The event recorder integrated in the HMI600 program (refer to chapter 4) registers special events of the ETL600 system, provides them with an accurate time stamp and stores the information sequentially into a non volatile memory. The resolution of the events which can be discriminated between is 1 ms.
  • Page 120: Nsd600 Command Events

    All these events are stored in the same block. The maximum number of command events is 2600. To upload the command events from the ETL600 equipment use: Equipment / Commissioning and maintenance / Event recorder / Upload events. 3-88...
  • Page 121: Alarm, Warning & Manipulation Events

    All these events are stored in the same block. The maximum number of alarm & manipulation events is 2600. To upload the alarm events from the ETL600 equipment use: Equipment / Commissioning and maintenance / Event recorder / Upload events.
  • Page 122: Upload Counters

    RTC synchronization from an external clock An external clock source can be supplied to increase the accuracy of the ETL600 system time. The clock signal has to be provided in the IRIG-B format at TTL compliant level and it has to be connected to the corresponding input on the front panel of the RF converter P4LT.
  • Page 123: Views

    So the date and time has to be set once manually in the ETL600 to supply the system with information about the current year. Refer to Set clock for the procedure about how to set the date and time.
  • Page 124: Set Up The Views

    1KHW001489-EN ETL600 ABB Switzerland Ltd • Zoom Mode: In/Out First you have to set up your views. After that you zoom out to find the events. Then zoom in to see information in a more detailed form. 3.7.9.3. Set up the views Press the right mouse button / Set up views.
  • Page 125: Import Events Into A Spreadsheet Or Word Processing Tool

    ETL600 1KHW001489-EN ABB Switzerland Ltd 3.7.9.7. Import events into a spreadsheet or word processing tool To import events into a third party tool (e.g. Microsoft® Excel): • Change to the events text view • Select the events to export and copy them to the clipboard (Ctrl+C), •...
  • Page 127: User Interface Program

    USER INTERFACE PROGRAM 4.1. Introduction The HMI600 software has been developed to program, tune, test, commission, operate and maintain the ETL600 equipment. It is a Windows based PC software with the user friendly features offered by the Windows environment. •...
  • Page 128: Installation

    XP or Windows 2000 operating system installed. A screen resolution of at least 1024 x 768 resolution is recommended. For communication with the ETL600 via cable or modem, one of the COM ports or USB ports of the PC should be free or the PC should have internet/intranet access via network card.
  • Page 129: Communication To The Etl600

    4.4.2. Direct connection via cable The easiest way for HMI600 to communicate with an ETL600 terminal is via cable. The PC must be equipped with a COM port or a USB port. In the latter case, a USB to RS-232 converter is required.
  • Page 130: Communication Media

    4.4.2.1. Communication media When directly connecting the PC to the ETL600, a one-to-one cable (9 pole female to 9 pole male) is used, provided the COM port of the PC has a 9 pole connector. In case the COM port of the PC has a 25 pole RS-232 connector, an adapter (25 pole female to 9 pole male) is needed.
  • Page 131: Logon To The Equipment

    Also make sure that the modems data format can be set to 8 data bits, even parity bit, one stop bit. 4.4.3.1.2. Cables For the connection between modem and ETL600, a 9 pin null modem cable has to be used: User Interface Program November 2005...
  • Page 132: Communication Settings

    In case the modem has a 25 pole RS-232 connector, an adapter (25 pole male to 9 pole female) is needed. On the ETL600, plug the cable into the HMI socket on the frontplate of P4LT.
  • Page 133: Configuration Of Hmi600

    ETL600 1KHW001489-EN ABB Switzerland Ltd to send the configuration commands to the modem. As these commands differ depending on the type of the modems used, it is not possible to specify a common configuration sequence for all modem types. Please refer to your modem dealer or the example below for further information.
  • Page 134: Logon To The Equipment

    As soon as the connection is made, the colour of the circle-button in the toolbar turns to green. 4.4.4. Communication via intranet/internet HMI600 can communicate with ETL600 via internet/intranet. Main control center Substation Internet, Intranet,...
  • Page 135: Configuration Of Hmi600

    That way, unauthorized access to the ETL600 from unknown clients is not possible. Click OK to accept the settings.
  • Page 136: Communication Media

    PC has a 25 pole RS-232 connector, an adapter (25 pole female to 9 pole male) is needed. For the connection between modem and ETL600, a 9 pin null modem cable as described in section 4.4.3.1.2 must be used. 4.4.5.2.
  • Page 137: Configuration Of Hmi600

    HMI ports of these terminals can be connected together via RS-485-bus available at the HMI port of P4LT at the ETL600 front as shown in Fig. 4-5. The PC must be connected via remote inquiry kit R7AP to the RS485 bus. Of course, this network of terminals can also be reached from a remote location according to Fig.
  • Page 138: Network Protocol

    Fig. 4-5. 4.5.3. Network protocol The network protocol used by the ETL600 terminals is connectionless. This means that all messages circulating in the network are routed to all terminals attached to the network. Only the addressed terminal will execute the commands contained in the message and generate an answer.
  • Page 139: Operation

    1KHW001489-EN ABB Switzerland Ltd A further valuable feature of the ETL600 network protocol is the possibility of connecting several PCs at various points to a network. In Fig. 4-8, in addition to the PC in the control center, another PC has been connected to the management port of terminal B1 in substation B.
  • Page 140: Data Management

    These documents can be found in the annex of this instruction manual. 4.7. Data management The configuration data of the ETL600 can reside in several locations: 1. In the RAM of a PC. As a data file on the hard disc of a PC or on other media.
  • Page 141: Compatibility

    To understand the explanations in the following sections, the terms 'ETL600 release', 'release number', 'version number', 'type code' need to be explained. An ETL600 system release, identified by a release number, is a product of defined functionality comprising hardware modules, firmware and software. Firmware and software are identified with version numbers of the form NN.nn., e.g.
  • Page 142: Compatibility Between Modules Of A Plc Terminal

    4.8.3. Compatibility between the two ETL600 terminals of a link The two ETL600 terminals of a link must belong to the same release. A warning 'Inconsistent firmware on local and remote equipment' will be generated by the terminals if this rule is not respected.
  • Page 143: Compatibility Of Hmi600 To Configuration Files

    Thus for each HMI600 version there is a compatibility range – shown graphically in Fig. 4-10 - containing all ETL600 releases and updates thereof to which it is compatible (fully or restricted).
  • Page 144: Uninstalling Hmi600

    1KHW001489-EN ETL600 ABB Switzerland Ltd files generated by HMI600 programs of a number of past releases. Updates of an HMI600 program will generally inherit the compatibility relations from its predecessors. The compatibility range of a specific HMI600 version– shown graphically in Fig. 4-11 – comprises all HMI600 versions whose configuration files can be opened by that version.
  • Page 145: Configuration And Set-Up

    The configuration of the ETL equipment including AF interfaces and teleprotection has to be done according to document 'Programming and Testing Instructions for the ETL600 Rel.1 Equipment'. The two major steps of the procedure are: Programming and Testing. Each of these steps consists of a number of substeps with associated instructions listed in the document.
  • Page 146: Power Definitions

    1KHW001489-EN ETL600 ABB Switzerland Ltd 5.2.1. Power definitions 5.2.1.1. Mean power The mean power of a signal with voltage x(t) is given by ⎧ ⎫ ∫ ⎨ ⎬ mean ⎩ ⎭ − → ∞ where R is the impedance at the point where the voltage x(t) is measured.
  • Page 147: Peak Voltage

    ETL600 1KHW001489-EN ABB Switzerland Ltd 5.2.2.2. Peak voltage The peak voltage of a signal with voltage x(t) is given by − ∞ < < ∞ peak 5.2.2.3. Peak envelope voltage In analogy to section 5.2.1.3 one can define the peak envelope voltage...
  • Page 148: Absolute Voltage Level

    (x) is given by equation (6). 5.2.4. Absolute level definitions - digital signal processing Within ETL600, most signal processing operations are executed by digital signal processors (DSPs). Continuous analog signals are represented by time sequences of sampling values. Each sampling value X(n) is a dimensionless digit in fixed or floating point representation.
  • Page 149: Absolute Psophometrically Weighted Level L 0P [Dbm0P]

    ETL600 1KHW001489-EN ABB Switzerland Ltd Absolute mean or RMS level: ⎛ ⎞ ⎧ ⎫ ⎜ ⎟ ∑ ∗ ⎨ ⎬ ⎜ ⎟ →∞ ⎩ ⎭ ⎝ − ⎠ ⎛ ⎞ ⎧ ⎫ ∑ ⎜ ⎟ ∗ (13) ⎨ ⎬ ⎜...
  • Page 150: System Power Level L 0 [Dbm0]

    Therefore, this impedance must be specified for each test socket of the equipment. For the ETL600, input impedances ≥ 5 kOhms (also referred to as “infinite”) or 50 Ohms are specified.
  • Page 151: Signal Weights

    ETL600 1KHW001489-EN ABB Switzerland Ltd (18) Example: For the test socket on the RF hybrid, we have A ts = 50 dB and the input impedance of the measuring set is specified to 50 Ohms. A measured voltage level L u|ts of -10 dBu indicates a power level L of 50 - 10 = 40 dBm equivalent to 10 Watts at the RF connector, which is the measuring point.
  • Page 152: The S-Value

    ABB Switzerland Ltd Table 5-1 lists the peak envelope system levels [dBm0 PE] and their associated weights for ETL600. It also gives the PE to mean level difference. All entries except “NSD600 test command signal” and “MOD600” must appear also in the signal selection dialog box for O4LE teleoperation ports of HMI600.
  • Page 153: Weight Of The Mod600 Signal

    ETL600 1KHW001489-EN ABB Switzerland Ltd ∑ (19) The following remarks have to be made to this equation: 1. The S-value describes the signals to be transmitted by the system while all active internal TPEs and all connected external TPEs are in the guard-state (quiescent state).
  • Page 154: Weight Of The Nsd600 Guard Signal

    18 dB below the PE power of the boosted NSD600 command signal. When the ETL600 pilot acts as NSD600 guard, it obtains the weight of the NSD600 guard signal, else the ETL600 pilot has the standard weight of 0.5.
  • Page 155: External Teleprotection Device Nsd570/Nsd70C

    APLC2 Table 5-3 Association of internal TPEs to channels Remark to Table 5-3: 1) TPE2 is not available when ETL600 is configured for 3 APLC channels in 8 kHz (refer to Table 3-1). 5.2.15. External teleprotection device NSD570/NSD70C The AF signals for NSD570/NSD70C are connected to O4LE ports configured for external teleprotection.
  • Page 156: Persistent Command Transmission With External Nsd570/Nsd70C

    NSD600 loop test command. Internal TPE – i.e. TPE integrated in ETL600 – are NSD600 devices. In case of two internal TPE, each of these gets half of the available output power for boosting.
  • Page 157: Boost Ratio

    1KHW001489-EN ABB Switzerland Ltd the ETL600. Signals occupying all or part of the band between 300 to 2000 Hz where an NSD600 device is operating must be discon- nectable, as this band must be kept free for transmission of the NSD600 tripping signals.
  • Page 158: Configuration With Hmi600

    Configuration with HMI600 In this section it is explained, how to create a configuration with the HMI600 for a ETL600 equipment. It is recommended to work through the next sections step by step. After this you will have created a configuration, which you should store in a file.
  • Page 159: Aplc Channels 1, 2 And 3

    - select the Number of ports that have to be supported. • In the frame External Teleprotection, - check the box External Teleprotection available, if such a device (e.g. NSD570) is to be conncted to the ETL600. 5.3.1.4. Internal teleprotection •...
  • Page 160: Configure System

    HMI600. Refer to section 4.5 for more details. • The default value for the HMI datarate in the ETL600 is 57600 bps. If this rate is changed, it must be changed accordingly in the HMI600 under Options / Communications.
  • Page 161 ETL600 1KHW001489-EN ABB Switzerland Ltd • For each command the following input command parameters can individually be configured and modified from the default settings: Tx Input Delay, Tx Input Prolongation, Max Tx Trip Duration. Pickup times for link and user alarms must be set to...
  • Page 162: Configure Analog Services

    1KHW001489-EN ETL600 ABB Switzerland Ltd • In the frame Command outputs during link failure it can be chosen how the command outputs should respond in case of a level or SNR alarm of the NSD600 concerned (TPE link alarm). Additionally a Pick up time (after the alarm condition has been detected) and a Hold time (after the alarm condition has disappeared) can be configured.
  • Page 163: Level Settings Of Teleoperation Ports, Introduction

    600 Ω, 75 Ω, … . For the system ETL600, the RMS levels have to be converted to Peak Envelope Power (PEP) levels expressed in dBm (PEP). With these PEP levels, the peak voltage at any point in the system can be determined and compared to the allowed maximum to avoid clipping.
  • Page 164: Configure Teleoperation Port Not Used For Transit Operation

    HMI600, the relative level is given for each configured teleoperation in- and output-port. The sum of the weightings of all signals to be transmitted by the ETL600, called the S- value, is also given in the configuration text. Refer to section 5.2.11 for more information about the S-value.
  • Page 165: Configure Teleoperation Port Used For Transit Operation

    ETL600 1KHW001489-EN ABB Switzerland Ltd 9. Select the Output level for your application. It is the input level of the external device connected to the port. 10. You should also check all other signals present at the output in the list named ‘...
  • Page 166 1KHW001489-EN ETL600 ABB Switzerland Ltd 3. Deactivate Squelch at SNR alarm. The squelch functionality should work nearby the port, where the external device is connected. Configure the transit filter: From the dialog 'Configure Teleoperation, ext. teleprotection’: 4. Select filter from the Output filter section.
  • Page 167: Configure Teleoperation Port Used For External Teleprotection

    ETL600 1KHW001489-EN ABB Switzerland Ltd the output level of the external device. Recommended values are –6.0 dBm or less. This input level must be configured as output level at Note: the other AF port connected to this AF port of the other equipment.
  • Page 168: Data Communication Services

    1KHW001489-EN ETL600 ABB Switzerland Ltd This is a general prerequisite for data communication with ETL600 and is explained in section 5.3.1.2. 5.3.5.1. Data Communication Services When APLC & DPLC channels are set, point to Configuration / Services… / Data Communication to select the quantity of required V.11 &...
  • Page 169: Data Port Parameter

    ABB Switzerland Ltd 5.3.5.3. Data Port Parameter 5.3.5.3.1. G.703 port Not supported with ETL600 Release 1. 5.3.5.3.2. V.11 ports When a DPLC channel has been configured, each available V.11 port can be assigned to a MOD600 channel, if the DPLC channel multiplexer is enabled.
  • Page 170: Ports

    1KHW001489-EN ETL600 ABB Switzerland Ltd 5.3.5.3.3. V.24 ports Any NSK600 modem that has been assigned to an APLC channel in Configuration / Services / Data communication is automatically assigned to the corresponding V.24 port and enabled. No further assignment of these ports is possible, nor can they be disabled without disabling the corresponding modem.
  • Page 171 • RP570/RP571 / FT1.2 : this is the configuration for SCADA applications using the ABB proprietary protocol RP570/RP571 based on IEC60870-1-5 FT1.2 with 8 data bits, 1 stop bit and even parity; •...
  • Page 172: Nsk600 Modem

    1KHW001489-EN ETL600 ABB Switzerland Ltd • Data Sensitive : This mode does not require handshaking signals from the DTE connected to the V.24 port. Dataflow from the TD terminal is connected to the corresponding transmission channel independently of its availability.
  • Page 173: Mod600 Modem

    ETL600 1KHW001489-EN ABB Switzerland Ltd • Status : • Off : the modem is not operational, communication is interrupted; • On – disconnectable : the modem is operational, communication will be interrupted during transmission of a teleprotection command; • On - non disconnectable : the modem is operational and communication will not be interrupted during transmission of a teleprotection command.
  • Page 174 1KHW001489-EN ETL600 ABB Switzerland Ltd The following signal settings can be configured for MOD600 modem with the appropriate selection of radio buttons or drop down list: • Status : • Off : the modem is not operational, communication is interrupted;...
  • Page 175: Use Of Hmi600 Files

    The default extension of such files is et6 . The data can be loaded back anytime into HMI600 from these files for modifications or for downloading to an ETL600 terminal connected to HMI600. To save the data to file, point to File / Save or File / Save As .
  • Page 177: Assembly And Installation

    ETL600 1KHW001489-EN ABB Switzerland Ltd ASSEMBLY AND INSTALLATION The installation of the equipment can only be successfully accomplished, if it is properly planned beforehand. Planning should not only take the present situation into account; future system expansion must also be included.
  • Page 178 1KHW001489-EN ETL600 ABB Switzerland Ltd The isolating terminals from the external cables DANGER must be kept open during installation, maintenance and before storage, decommissioning and disposal. Faston plugs on the cables connected to the rack DANGER P7LA must be covered with an isolation sleeve.
  • Page 179 PCB Extenders For measuring purposes only the original PCB DANGER extenders P4LM, P3LL and I9BK, designed to work with ETL600 equipment, must be used. ESD protection The modules in this equipment contain devices, Caution which can be damaged by electrostatic discharges.
  • Page 180 1KHW001489-EN ETL600 ABB Switzerland Ltd Power supplies connected to alarm relay contacts Caution must be short circuit and over current protected. P1LA Hazardous voltages and/or hazardous energy level DANGER at the heat sink. Do not touch during operation. Heat sink should not be touched with conducting...
  • Page 181: Unpacking And Transport

    Visually inspect all the material when unpacking it. Where there is evidence of transport damage, lodge a claim immediately in writing with the last carrier, notify the nearest ABB company or agent and also ABB Switzerland Ltd, address to be found in document 1KHM010296 Repair an Return Procedure in the annex.
  • Page 182: Grounding System

    1KHW001489-EN ETL600 ABB Switzerland Ltd pedestal or as a suite of cabinets on a platform to facilitate cleaning of the floor and routing of cables. 6.4.1. Grounding system The grounding system must go out radially from the station ground rail.
  • Page 183: Photographs

    6.5. Photographs The following photographs may be used for reference when assembling an ETL600 equipment. The installation is shown for an E40A type cabinet, but other installation schemes are possible. Fig. 6-1 Front view of the ETL640 equipment equipped with interfaces O4LE...
  • Page 184: Fig. 6-2 Front View Of Etl640 Mounted In A Cabinet Type E40A

    1KHW001489-EN ETL600 ABB Switzerland Ltd Fig. 6-2 Front view of ETL640 mounted in a cabinet type E40A Power rack P7LA V9MX RF cable V9MY flat band cable (with EMI filter) Optional alarm module R1BC Channel rack P7LC, with rear cover opened Fig.
  • Page 185: Fig. 6-4 Front View Of Etl680 Mounted In A Cabinet Type E40A

    ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 6-4 Front view of ETL680 mounted in a cabinet type E40A Upper power rack P7LA Flat band cable V9LH Jumper cable V9LN (3 wires) RF connector (80 W) Lower power rack P7LA V9MY flat band cable...
  • Page 186: Connections

    1KHW001489-EN ETL600 ABB Switzerland Ltd Supply cable V9MT Supply cable V9LL Fig. 6-6 Side plate of power subrack P7LA with supply connections Fig. 6-7 The plate A9CS for connection of external RF coaxial cable 6-10 November 2005 Assembly and Installation...
  • Page 187: Fig. 6-8 The Terminal Block For Connection Of Power Supply

    ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 6-8 The terminal block for connection of power supply Fig. 6-9 Terminal block of cable V9OF for NSD600 Assembly and Installation November 2005 6-11...
  • Page 188: Fig. 6-11 Krone Type Terminal Block Used For Data Or Telephony Interfaces

    1KHW001489-EN ETL600 ABB Switzerland Ltd Fig. 6-10 The cabinet bottom Fig. 6-11 Krone type terminal block used for data or telephony interfaces All cables are mechanically secured to the earth plate by plastic cable binders. Shield clamps are used to galvanically connect the cable shields to the earth plate.
  • Page 189: Fig. 6-12 Earth Rail R9Al Mounted In The Bottom Rear Of The Channel Subrack P7Lc

    ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 6-12 Earth rail R9AL mounted in the bottom rear of the channel subrack P7LC All cables are mechanically secured to the earth rail by plastic cable binders. Shield clamps are used to galvanically connect the cable shields to the earth rail.
  • Page 190: External Connections

    Cover for unused faston HESG455631P0001 The ETL600 can be equipped with the unit B5LA for 48 V DC supply or with the unit B5LC for 115/230 V, 50/60 Hz AC supply. The connections will be accordingly, either to the DC or the AC...
  • Page 191: Interfaces

    ETL600 1KHW001489-EN ABB Switzerland Ltd 6.6.3. Interfaces Connections to the various interfaces are made with cables equipped with connectors or connector blocks that are normally mounted in the back of the cabinet. The following table lists the interfaces and the corresponding cables.
  • Page 192: Af Interface O4Le

    1KHW001489-EN ETL600 ABB Switzerland Ltd ***) Also available without LSA Plus Quick Connect (Krone) with lengths of 3, 10 or 20 m to be used for terminating on main distribution frame. LSA Quick Plus quick connect is manufactured by KRONE. With this system the connections to the AF interfaces can be made quickly without soldering.
  • Page 193 ETL600 1KHW001489-EN ABB Switzerland Ltd There are four 4-wire input / output ports available: AF1, AF2, AF3 and AF4. Port AF1 is normally used for telephony. When speech is not necessary this port can be used for teleoperation channel. Port AF1: Input –...
  • Page 194 1KHW001489-EN ETL600 ABB Switzerland Ltd Fig. 6-13 Connections for AF interface O4LE The cable V9OD has identical pinout, but the colors are different. 6-18 November 2005 Assembly and Installation...
  • Page 195: Teleprotection Interface G4Ai

    ETL600 1KHW001489-EN ABB Switzerland Ltd 6.6.3.2. Teleprotection Interface G4AI The teleprotection interface includes: • Four input circuits equipped with optocouplers • Four output circuits equipped with MOS – FET semiconductor • Two output relays These circuits are available for customer connections by means of cable V9OF, shown in Fig.
  • Page 196: Fig. 6-14 Connections For Teleprotection Interface G4Ai

    1KHW001489-EN ETL600 ABB Switzerland Ltd Fig. 6-14 Connections for teleprotection interface G4AI 6-20 November 2005 Assembly and Installation...
  • Page 197: Rf Converter P4Lt/P4Lu

    ETL600 1KHW001489-EN ABB Switzerland Ltd 6.6.3.3. RF Converter P4LT/P4LU The data interface sockets of the RF converters P4LT/P4LU are located at the front plate. Three types of sockets are used: • Sub-D 15 pole for V.11 ports, • Sub-D 9 pole for HMI port (RS-232 or RS-485), IRIG-B port and V.24 ports,...
  • Page 198: V.24 Cable V9Ou

    1KHW001489-EN ETL600 ABB Switzerland Ltd 6.6.3.3.2. RS-232 / V.24 cable V9OU Fig. 6-16 RS-232 / V.24 cable connected to HMI port 6-22 November 2005 Assembly and Installation...
  • Page 199: Fig. 6-17 Rs-232 / V.24 Cable Connected To V.24 Port

    ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 6-17 RS-232 / V.24 cable connected to V.24 port Assembly and Installation November 2005 6-23...
  • Page 200: Irig-B Cable V9Ov

    1KHW001489-EN ETL600 ABB Switzerland Ltd 6.6.3.3.3. RS-485 / IRIG-B cable V9OV Fig. 6-18 RS-485 / IRIG-B cable connected to HMI port (station bus) Fig. 6-19 RS-485 / IRIG-B cable connected to IRIG-B port 6-24 November 2005 Assembly and Installation...
  • Page 201: Alarm Relays Cable V9Ot

    ETL600 1KHW001489-EN ABB Switzerland Ltd 6.6.3.3.4. Alarm relays cable V9OT Fig. 6-20 Connections to the alarm relays of P4LT Connecting a load between terminals NO (normally Caution open) and NC (normally closed) is not allowed. Use only one contact set NO or NC.
  • Page 202: Relay Module R1Bc

    HMI600 to respond to a desired combination of alarm criteria. All alarm relays in the ETL600 equipment are picked up during a no fault condition. This is indicated with a dashed line on the alarm contact.
  • Page 203: Fig. 6-21 Connections To The Alarm Relay Module R1Bc

    ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 6-21 Connections to the alarm relay module R1BC Assembly and Installation November 2005 6-27...
  • Page 204: Remote Inquiry Kit R7Ap

    The remote inquiry kit R7AP allows to connect RS-232 ports to an RS- 485 station bus, for element management networking as described in Chapter 4 ' User Interface Program '. While ETL600 has its RS-485 bus signals available at the HMI connector on the frontplate of P4LT, ETL500 requires R7AP for conversion of RS-232 to RS-485 interface signals.
  • Page 205: Fig. 6-23 Connections For Remote Inquiry Kit R7Ap

    ETL600 1KHW001489-EN ABB Switzerland Ltd Fig. 6-23 Connections for remote inquiry kit R7AP Assembly and Installation November 2005 6-29...
  • Page 207: Commissioning

    ETL600 1KHW001489-EN ABB Switzerland Ltd COMMISSIONING 7.1. Safety instructions Personnel qualification An authorized and properly trained personnel only is DANGER admitted to carry out installing, programming, commissioning, maintenance, troubleshooting and work of the equipment. Mechanical Installation The equipment must be mounted in a cabinet.
  • Page 208 PCB Extenders For measuring purposes only the original PCB DANGER extenders P4LM, P3LL and I9BK designed to work with ETL600 equipment, must be used. ESD protection The modules in this equipment contain devices, Caution which can be damaged by electrostatic discharges.
  • Page 209: Checking The Line Of Communication

    ETL600 1KHW001489-EN ABB Switzerland Ltd P4LT/P4LU Hazardous voltages and/or hazardous energy level DANGER on the module and the cable. Do not touch the module and the cable leads. R1BC Hazardous voltages and/or hazardous energy level DANGER on the module and the cable.
  • Page 210 1KHW001489-EN ETL600 ABB Switzerland Ltd It is defined by the following equation: − rated impedance actual input impedance A low value signifies a poor match, which results in a reduced transfer of power from the PLC transmitter onto the transmission line. The main disadvantage, however is the intermodulation phenomenon and associated cross-talk it causes.
  • Page 211 ETL600 1KHW001489-EN ABB Switzerland Ltd Appreciable discrepancies between the measured results and the nominal characteristic point to defective components and the filters must be checked individually. SELECTIVE LEVEL METER SPM 32/33 Dummy load Input Nominal output impedance Rec. impedance: appr. 5 kOhm e.g.
  • Page 212 1KHW001489-EN ETL600 ABB Switzerland Ltd Return loss a Fig. 7-3 Typical return loss characteristic under practical conditions with the transmission line as load Return loss a Fig. 7-4 Typical return loss characteristic at rated load November 2005 Commissioning...
  • Page 213: Line Attenuation

    ETL600 1KHW001489-EN ABB Switzerland Ltd Return loss: phase-to-ground coupling filter Z0 + Z Return loss = 20 log Z0 - Z impedance meter rated impedance actual input impedance Fig. 7-5 Test circuit using a dummy load for measuring return loss in the case of single-phase coupling...
  • Page 214 1KHW001489-EN ETL600 ABB Switzerland Ltd grounded behind the line traps. The test circuit is shown in Fig. 7-7 and Fig. 7-8. Unexpectedly high attenuation or fluctuations of attenuation of several dB's within just a few kHz would indicate a defective line trap or extremely unusual characteristics of the line itself.
  • Page 215: Commissioning Of The Plc Equipment

    Tests according to the commissioning instructions The equipment was carefully tested and calibrated according to document ‘Programming and Testing Instructions ETL600 Rel. 1’ prior to delivery and therefore all the internal signal levels will already be at their correct values. Thus only those settings need to be carried out, which are influenced by the practical operating conditions on site.
  • Page 217: Operation And Maintenance

    ETL600 1KHW001489-EN ABB Switzerland Ltd OPERATION AND MAINTENANCE 8.1. Safety instructions Personnel qualification An authorized and properly trained personnel only is DANGER admitted to carry out installing, programming, commissioning, maintenance, troubleshooting and work of the equipment. Warning labels Precautions and indications to hazardous voltages...
  • Page 218 PCB Extenders For measuring purposes only the original PCB DANGER extenders P4LM, P3LL and I9BK, designed to work with ETL600 equipment, must be used. ESD protection The modules in this equipment contain devices, Caution which can be damaged by electrostatic discharges.
  • Page 219 HMI600. Appropriate measures have to be taken especially in case protection signal transmission is being used. During routine tests with the ETL600 in operation Caution the “ Reset ” item in the Equipment menu of the...
  • Page 220 1KHW001489-EN ETL600 ABB Switzerland Ltd O4LE The phone interface on the module O4LE generates DANGER dangerous voltage up to 100 V. Don’t operate the module without upper and lower cover plate. Do not touch the open pins of the service phone connector, the leads of its cable, the pins of the external cable connector and the leads of the external cable.
  • Page 221: Operation

    Faulty Operation Refer also to chapter 9 ' Troubleshooting '. If the ETL600 system is in normal operation, a green LED ‘RDY’ on the front plate of P4LT is on to indicate that the system is ready. A faulty operation will be indicated by red LEDs. In case there is a fault on the line or with the modules, red LEDs in the field above the ‘HMI’...
  • Page 222: Maintenance

    B5LA/B5LC is within tolerance. 8.3.1.2. Check alarm status for ETL600 element management networks To check the alarm status of a number of ETL600 terminals forming an element management network, the function 'Alarm polling' (menu November 2005 Operation and Maintenance...
  • Page 223: Check Alarm Events

    8.3.1.3. Check alarm events The alarms stored by the built in event recorder of the ETL600 terminals can be inspected. Upload the stored events by activating Equipment / Commissioning and maintenance / Event recorder / Upload events .
  • Page 224 During this time no commands can be transferred. During routine tests with the ETL600 in operation Caution the " Reset " item in the Equipment menu of the...
  • Page 225 ETL600 1KHW001489-EN ABB Switzerland Ltd 10. If required, synchronize the trip counters in local and remote stations by resetting them via HMI600 (menu Equipment / Commissioning and maintenance / Event recorder / Reset counter -> reset all counters). c) Checking the entire link:...
  • Page 227: Troubleshooting

    ETL600 1KHW001489-EN ABB Switzerland Ltd TROUBLESHOOTING In case of failure of communications between the two stations of the PLC link, the fault could either be caused by the power line itself, either or both of the PLC equipment or the coupling arrangement. A systematic approach helps in tracking the fault in the shortest possible time.
  • Page 228 PCB Extenders For measuring purposes only the original PCB DANGER extenders P4LM, P3LL and I9BK designed to work with ETL600 equipment, must be used. ESD protection The modules in this equipment contain devices, Caution which can be damaged by electrostatic discharges.
  • Page 229 ETL600 1KHW001489-EN ABB Switzerland Ltd B5LC Make sure that the power supply B5LC is DANGER programmed to the correct voltage of 230 V AC or 115 V AC as described in 1KHL015788 before connecting the equipment to the power source.
  • Page 230: Fuses

    T 6.3 A/250 V Table 9-1 Fuses in the equipment 9.3. Alarms The alarm concept of the ETL600 system is designed to • detect and locate the sources responsible for abnormal operation of the system, • provide information about the kind of problems detected.
  • Page 231: Alarm Concept

    A warning indicates that the ETL600 terminal is not in the normal operation state. An example for this is when the ETL600 terminal operates in a test mode. An event is a snapshot of the alarm state of the ETL600 terminal recorded together with date and time. Troubleshooting...
  • Page 232: Warnings

    Warning LEDs are provided on the front plates of P4LT, O4LE and G4AI. Their colour is yellow. 9.3.3. Grouping of alarms Alarms and warnings can be grouped according to several criteria (Fig. 9-3): • Service: PLC, TPE1, TPE2, DATA • Hardware: Circuit boards of the ETL600 terminal November 2005 Troubleshooting...
  • Page 233: Grouping Of Alarms

    DATA alarms relate to data transmission only, i.e. the subsystems MOD600, MUX600, NSK600 and associated data interfaces. • PLC alarms relate to the core functions of the ETL600 terminal as well as to the analog services telephony, teleoperation, external teleprotection.
  • Page 234: Affected Hardware

    RF signal is insufficient. For other interface connectors, specific interface alarms are issued in case the ETL600 detects that the signal at the connector is out of specification. Examples of such signals are: •...
  • Page 235: Alarm Outputs

    ETL600 1KHW001489-EN ABB Switzerland Ltd • Warnings: A pickup time of 10 s and a hold time of 1 s are used for warnings. Pick up time Hold time High-level alarm Fig. 9-4 Derivation of high-level alarms 9.3.7.3. Low-level alarms/warnings Most low-level alarms/warnings are directly generated by a hardware device or a software process.
  • Page 236: Alarm Led On G4Ai

    1KHW001489-EN ETL600 ABB Switzerland Ltd Colour Description Lights continuously while the system is in normal operating condition. Green: Otherwise it is flashing. Lights up when the top-level Warning is Yellow active. Lights up when the top-level SYSTEM alarm is active.
  • Page 237: Alarm Relays On R1Bc

    HMI600 to any combination of high-level alarms and warnings of the local and the remote ETL600 terminal. As shown in Fig. 9-2, the high-level alarms of the remote terminal are transmitted via EOC to the local terminal.
  • Page 238: Alarm Event Recorder

    All alarms/warnings except detail alarms are recorded as events in non-volatile memory on P4LT. An alarm event is a snapshot of the ETL600 alarm state together with a date/time stamp. The recorded events can be uploaded to the PC and viewed with the help of the HMI600 program.
  • Page 239: Internal Teleprotection Equipment

    The event recorder can be synchronized to an external GPS receiver for accurate time stamping in all the different locations where ETL600 equipment is used. Therefore it is possible to directly compare and analyze the logs of several ETL600/NSD600 devices in a network where a failure occurred.
  • Page 240 1KHW001489-EN ETL600 ABB Switzerland Ltd Question: The PLC link doesn't work. What can I do to correct this problem? Answer: Check the alarms: If there is a hardware alarm at either side of the link, the reason of it must be found and the problem corrected.
  • Page 241: List Of Alarms And Corrective Actions

    ETL600 1KHW001489-EN ABB Switzerland Ltd Module R1BC, i.e. the “alarm” condition is the same as the “power off” state of the equipment (relay coil not energized). On all modules the user can still choose – by using the corresponding output contacts - whether the alarm contact shall be “normally open”...
  • Page 242: Plc

    • NSK600 DSP stopped working Connect the shields of cables to ETL600 to ground as • MOD600 DSP described in section 6. Improve the grounding of ETL600, specially the connections between the buried earth grid...
  • Page 243 • +3.3 V overvoltage Disconnect all cables to P4LT. Switch off the power to • +1.8 V undervoltage ETL600 and switch it on again after some seconds. If the • +1.8 V overvoltage error persists, replace P4LT. • Event recorder not Storing of events to the nonvolatile flash memory wasn’t...
  • Page 244: Plc Link Alarms

    At least one of the O4LE boards reports an alarm. alarm Switch off the power to ETL600 and switch it on again after some seconds. If the error persists, find the faulty O4LE board(s) by studying the TDM bus communication alarms (section 9.6.4).
  • Page 245: Plc Interface Alarms

    ETL600 1KHW001489-EN ABB Switzerland Ltd HMI600 Alarm Text Explanation and corrective actions (the latter in italics) • Low Rx pilot level in The Rx pilot level on channel 1/2/3 is below the alarm threshold. channel 1 • Low Rx pilot level in...
  • Page 246: Plc Warnings

    Commissioning and maintenance / Test PLC-link is tone(s) switched on active. • Equipment in tuning The ETL600 is not in normal operation mode. Reasons for that might be or testing mode - any test switch is active, - any Tuning and Testing procedure is ongoing,...
  • Page 247: O4Le Detail Alarms

    The UART / PLL is not / the CODECS are not properly working. UART failed • Initialization of PLL Switch off the power to ETL600 and switch it on again after failed some seconds. If the error persists, replace the faulty O4LE •...
  • Page 248: O4Le Detail Warnings

    EMI, possibly in combination with poor substation grounding and/or not properly grounded cable shields. Connect the shields of cables to ETL600 to ground as described in 6. Improve the grounding of ETL600, specially the connections between the buried earth grid and substation ground, substation ground and cabinet, cabinet and (swing) frame, (swing) frame and equipment rack.
  • Page 249: Data Link Alarms

    CRC error Connect the shields of cables to ETL600 to ground as described in section 6. Improve the grounding of ETL600, specially the connections between the buried earth grid and substation ground, substation ground and cabinet, cabinet and (swing) frame, (swing) frame and equipment rack.
  • Page 250: Data Interface Alarms

    1KHW001489-EN ETL600 ABB Switzerland Ltd HMI600 Alarm Text Explanation and corrective actions (the latter in italics) MOD600 data transmission is stopped because the local • MOD600 MOD600 receiver can’t synchronize to the signal arriving synchronization from the remote MOD600 Tx.
  • Page 251: Data Warnings

    Connect the shields of cables to ETL600 to ground as described in section 6. Improve the grounding of ETL600, specially the connections between the buried earth grid...
  • Page 252: Tpe Link Alarms

    1KHW001489-EN ETL600 ABB Switzerland Ltd HMI600 Alarm Text Explanation and corrective actions (the latter in italics) • G4AI hardware An alarm is present on one of the G4AI boards alarm Check G4AI status for detailed information. 9.6.3.2. TPE link alarms...
  • Page 253: Tpe Warnings

    ETL600 1KHW001489-EN ABB Switzerland Ltd HMI600 Alarm Text Explanation and corrective actions (the latter in italics) • Max Rx command A command has been received of duration longer than the duration exceeded configured maximum (e.g. Configuration / NSD600 / Alarm TPE1 / Command outputs during link failure ) s been exceeded.
  • Page 254: G4Ai Detail Interface Alarms

    A hardware error at one of the solid state outputs has been detected. output 1-4 Switch off the power to ETL600 and switch it on again after some seconds. If the error persists, replace the faulty board. • Max Tx command The length of at least one Tx command applied to command inputs exceeds the max.
  • Page 255: G4Ai Detail Warnings

    ETL600 1KHW001489-EN ABB Switzerland Ltd 9.6.3.7. G4AI detail warnings HMI600 Alarm Text Explanation and corrective actions (the latter in italics) • Active configuration A test configuration for the board is active which will be lost when the associated test configuration timer runs out.
  • Page 256: Dispatch For Repairs

    Dispatch for repairs A module identified and confirmed to be faulty should be sent for repairs to ABB. It should be packed preferably in the original packing or in anti-static bags with additional mechanical protection to avoid damage during transport. It should be accompanied by a short description of the observed fault.
  • Page 257: Storage, Decommissioning And Disposal

    ETL600 1KHW001489-EN ABB Switzerland Ltd STORAGE, DECOMMISSIONING AND DISPOSAL 10.1. Safety instructions Personnel qualification An authorized and properly trained personnel only is DANGER admitted to carry out installing, programming, commissioning, maintenance, troubleshooting and work of the equipment. Mechanical Installation The equipment must be mounted in a cabinet.
  • Page 258: Storage

    ETL600 subrack and the terminal blocks. Now dismount the subrack by unscrewing the screws from the front. • If the ETL600 subrack or its modules are to be reused, they should be handled and packed properly following precautions for ESD protection.
  • Page 259: Options

    ETL600 1KHW001489-EN ABB Switzerland Ltd OPTIONS 11.1. Basic equipment The basic ETL600 equipment without any interfaces consists of Module Description ETL640 ETL680 Channel subrack type P7LC DC-DC-converter type B4LE RF converter P4LT Receive filter type P4RX (optional when Tx and Rx...
  • Page 260: Dummy Load P3Lk

    1KHW001489-EN ETL600 ABB Switzerland Ltd 11.2.1.5. Dummy load P3LK The transmitter is looped to the own receiver by inserting the dummy load P3LK in place of the RF hybrid P3LE, which enables both transmitter and receiver to be fully tested.
  • Page 261: Optional Facilities

    Windows environment. Refer to chapter 4 for details about HMI600. 11.2.2.2. Cabinet type E40A with accessories The ETL600 can be mounted in the E40A type of cabinet which also includes various accessories such as rails for mounting terminal blocks, cable channels etc.
  • Page 262: Service Telephone Q8Ab

    AF interface O4LE. 11.3. Licenses The basic equipment ETL600 contains all the functions described in this Instruction Manual, but with MOD600 and NSK600 modems disabled. License keys need to be ordered depending on how many modems are required.
  • Page 263 ETL600 1KHW001489-EN ABB Switzerland Ltd ANNEX TO ETL600 REL.1 INSTRUCTION MANUAL Contents Compatibility Requirements 1KHW001490-EN Tuning Instructions for Rx RF Filter P4RX 1KHW001491-EN Tuning Instructions for Tx RF Filter E5TX 1KHW001492-EN Instruction for Changing the Input Voltage of B5LC 1KHL015788-EN...
  • Page 265 PC based software, implementing the user interface for configuration, testing and monitoring of the equipment. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd...
  • Page 266 • Rule Nr. 1: The modules of an ETL600 terminal and the firmware on these modules must belong to the same release as given by Table 1. If an equipment contains modules of different releases, it will generally not work correctly.
  • Page 267 Rel. 1.0.1 Software SVR600 version 1.00 or higher (for PC with Windows 2000 or XP), Firmware ETL600 version 1.28 or higher on module P4LT/P4LTa or P4LU/P4LUa, Microcontroller firmware version 1.10 or higher on module P4LT/P4LTa or P4LU/P4LUa, Firmware O4LE version 2.14 or higher on module O4LE/O4LEa, Firmware G4AI version 3.00 or higher on module G4AI/G4AIa,...
  • Page 269 • The same Rx tuning adapter P4LM used for ETL 41 and ETL500 can be used for ETL600. However, if two shorting wires are present on the P4LM, they must be removed. The position of these 2 shorting wires - if present - will be across C1-C9 &...
  • Page 270: General

    2.1 Steps for determining the required jumper positions If not already done, switch on the power of the ETL600, start up the HMI600 on the PC, log on to the local ETL600 using equipment ID 0 and Read & write access, Upload configuration as well as Upload status enabled.
  • Page 271: Tuning The Filter Circuits Individually

    P4RX is plugged on top of P4LM. If not already done, switch on the power of the ETL600, start up the HMI600 on the PC, log on to the local ETL600 using equipment ID 0 and upload configuration and status of the equipment.
  • Page 272: Checking The Gain And Frequency Response Of The Filter

    Revision: Language: Page: 1KHW001491-EN 11. Using a plastic screwdriver, slowly turn the adjuster screw of coil L1, until the voltage at the level meter is minimized. The coil L1 is tuned now. 12. Select coil L2 by setting jumper S3 on P4LM to position L3(!) and repeat the procedure by clicking Activate f2 to tune coil L2 of P4RX.
  • Page 273: 4.2 Steps To Check The Frequency Response

    Revision: Language: Page: 1KHW001491-EN Connect the BNC connector OUT of P3LL with the RX RF-IN (50 Ohm input) SSMB connector on the P4RX board. Connect the level meter 50 Ohm (or 75 Ohm) to the RX RF-OUT (50 Ohm output) SSMB connector of the P4RX board.
  • Page 274: Test Circuits

    Revision: Language: Page: 1KHW001491-EN Test circuits P1LA RF Hybrid P4LT FILTER not to be plugged TUNE FILTER FUNCTION P3LL Ext.Coaxial Cable TUNE NORM FILTER P4RX P4LM P7LC OUTPUT 50 / 75Ω/∞ Figure 1: Test circuit for tuning L1 and L2 on P4RX Notes: For checking the signal path from P4LT to BNC IN of P4LM, switch S1 of P4LM can be put to position SET.
  • Page 275 Revision: Language: Page: 1KHW001491-EN P1LA RF Hybrid P4LT FILTER not to be plugged TUNE FILTER FUNCTION P3LL P4RX External coaxial cable BNC-SSMB RX RF-IN RX RF-OUT External coaxial cable BNC-SSMB P7LC OUTPUT 50/75Ω (selective) Figure 2: Test circuit for verifying the P4RX filter and gain settings The P4RX board is plugged directly in the rack, without tuning adapter.
  • Page 277 Please refer to 1KHW001490 for compatibility between software HMI600, Note: firmware and hardware of ETL600. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd...
  • Page 278: General

    Steps for determining the required jumper positions If not already done, switch on the power of the ETL600, start up the HMI600 on the PC, log on to the local ETL600 using equipment ID 0 and Read & write access, Upload configuration as well as Upload status enabled.
  • Page 279: Tuning The Filter Circuits Individually

    If not already done, switch on the power of the ETL600, start up the HMI600 on the PC, log on to the local ETL600 using equipment ID 0 and upload configuration and status of the equipment.
  • Page 280 Revision: Language: Page: 1KHW001492-EN Click Tune Tx RF filter to get the Tuning Tx RF filter dialog box. Check if the correct filter center frequency f0 and bandwidth are shown. For tuning the coil L1 in the lower rack set the adapter P3LL to: •...
  • Page 281: Checking The Frequency Response On 40 W Or 80 W Unit

    If not already done, switch on the power of the ETL600, start up the HMI600 on the PC, log on to the local ETL600 using equipment ID 0 and upload configuration and status of the equipment.
  • Page 282: Test Circuits

    Revision: Language: Page: 1KHW001492-EN Test circuits The following circuits should be used for tuning the Tx RF filter using the tuning adapter P3LL and the HMI600. The P4LT/P4LU generates the required tuning tones. Test circuit for 40 W units P1LA E5TX FILTER P3LE...
  • Page 283 Revision: Language: Page: 1KHW001492-EN P1LA P1LA E5TX OFF ON FILTER P4LT/U P3LE TUNE FILTER P3LL OUTPUT 600134A5.VSD Fig. 3: Test circuit for tuning L2 in the lower power amplifier rack. P1LA E5TX P3LG P1LA FILTER P4LT/U P3LE TUNE FILTER P3LL OUTPUT 600134A6.VSD Fig.
  • Page 285 Operate the module only in the condition specified by the manufacturer. Caution We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd...
  • Page 286 5) Insert two wire bridges X13-X14 and X15-X16 for 115 VAC 6) Insert two new fuses F1 and F3: 4 A slow-blow (ABB part no. XN 400018P0022) 7) Close the module by adding the cover and fixing it with the four bolts...
  • Page 287 The connections for the tests can be made either at the test sockets on the front of the equipment or at the terminals. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd...
  • Page 288 Equipment Lower frequency, usually meant as low cut-off frequency Light Emitting Diode found on the front panel HMI600 User Interface Program for ETL600 running on a PC N11, …, N71 Position in rack. Slot number N11, …, N71 Receiver Transmitter Personal Computer X11, …, X71...
  • Page 289 Typically this data are configured off-line and stored as a file on a disk. All these settings are loaded from a file – the ETL600 configuration file *.et6 – and downloaded to the equipment. The download of hardware settings such as jumpers or the presence or absence of modules without access to the TDM bus is just for documentation and the correctness of this information must be verified in the course of this instruction.
  • Page 290 Revision: Language: Page: 1KHW001493-EN 4/37 A.3.4 Assemblies in rack P7LC Check in the configuration file (View / Display hardware settings only / Modules and assemblies in rack P7LC) if the number and type of boards corresponds to the hardware. The number of O4LE and G4AI boards depend on the entries made in the dialog box Configuration / Services.
  • Page 291 (also called ‘retainer’) on P4LT/P4LU. Six different colors of the device exist. Refer to the ETL600 instruction manual 1KHW001489 at the end of chapter 11 for more information. The number of required MOD600 and NSK600 modems decides about the color of the needed license key, which is displayed in the configuration file (View / Display hardware settings only./...
  • Page 292 Revision: Language: Page: 1KHW001493-EN 6/37 If no license key is installed at all, you can skip step 3 of the following description: 1. Switch off the equipment. 2. Loosen the four mounting screws and pull out module of type P4LT/P4LU. 3.
  • Page 293 Testing Instructions for the ETL600 Rel. 1 Equipment. General Most of the testing for the ETL600 system can be done with assistance of HMI600. For some adjustments like Tx RF level, Rx RF level etc. the permissible limits are calculated by the HMI600 and displayed in the dialog boxes.
  • Page 294 HMI600 must be used and/or the firmware of some modules must be upgraded. The latter is described in the document ‘Firmware Download ETL600 Rel. 1’, 1KHW001496. If the download operation is possible, a message box appears, which informs you that the link will be cut off for a few seconds.
  • Page 295 Revision: Language: Page: 1KHW001493-EN 9/37 B.5.3 Adjust Tx RF level The Tx RF level is adjusted using the HMI600, a level meter and a termination resistor or attenuator. In the Tuning & testing dialog box click Adjust Tx RF level. This opens the Adjust Tx RF level dialog box.
  • Page 296 Tuning is only necessary for high performance measurements, for a custom approval of the equipment or for long power lines with high signal attenuation. Note: The tuning is not necessary when the ETL600 is operated without Rx filter P4RX. If the hybrid is not tuned, default settings must be used: Set the line balancing network jumpers RA, LP, CD and CE und put the remaining C-jumpers in P position.
  • Page 297 Revision: Language: Page: 1KHW001493-EN 11/37 If no minimum could be achieved with LA to LN, reduce the level using jumpers CA – CN until the next minimum is reached. The capacitors are binary weighted with CA the smallest and CN the largest capacitor. C jumpers may be inserted in parallel. Conclude the tuning by adjusting R226 for the next minimum.
  • Page 298 Revision: Language: Page: 1KHW001493-EN 12/37 B.8.2 Testing external real time clock synchronisation (if available) The external clock source with IRIG-B format has to be connected to the IRIG-B port at the frontplate of P4LT/P4LU via external cable V9OV. Testing the external synchronisation using HMI600: Set the time on the PC a few hours back/forward On the Equipment menu point to Commissioning and maintenance menu point to Eventrecorder and click Set Clock.
  • Page 299 Revision: Language: Page: 1KHW001493-EN 13/37 B.9.3 NSD600 loop test The NSD600 is tested by issuing a loop test via HMI600. In the Commissioning & maintenance … dialog box click NSD600 send loop test / TPE1 and – if TPE2 is configured – NSD600 send loop test / TPE2. If the loop test is successful, a dialog box indicating the loop test time (T ) appears.
  • Page 300 Revision: Language: Page: 1KHW001493-EN 14/37 EUT: O4LE remote 5.5 H 110 µF Audio Analyzer 110 µF 5.5 H Generator Analyzer 110 µF EUT: O4LE local 5.5 H 110 µF 110 µF 5.5 H 110 µF SUBSCR_Mess3.dsf Figure 2 B.10.3 ‘Remote subscriber’, remote is Pax 2-wire The following tests must only be done, if the operation mode ‘Remote subscriber’...
  • Page 301 Revision: Language: Page: 1KHW001493-EN 15/37 EUT: O4LE R = 2k2 remote 5.5 H 110 µF Audio Analyzer 110 µF 5.5 H Generator Analyzer 110 µF U = 50 V EUT: O4LE local 5.5 H 110 µF 110 µF 5.5 H 110 µF SUBSCR_Mess4.dsf Figure 3...
  • Page 302 Revision: Language: Page: 1KHW001493-EN 16/37 Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be closed. Check it. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a should be closed and contacts 6a-6b should be open. Switch off the remote equipment, after the programmed delay time the link alarm occurs.
  • Page 303 Revision: Language: Page: 1KHW001493-EN 17/37 Feed a 800 Hz tone, with the configured level from remote side into AF1-IN of remote equipment. Take a measurement of the output level at AF1-OUT of the local equipment. It should be in 1 dB range of the configured output level from the local equipment. Take a measurement of the output level at P2W-OUT of the local equipment.
  • Page 304 Revision: Language: Page: 1KHW001493-EN 18/37 Applying the second method to the configuration given below, a sinus with –9.0 dBm is fed into remote equipment. Calculating the expected output level at local equipment with the formula above results to: = -9.0 dBm – (-4.00 dBr) + (-1.00 dBr) The expected output level L is just as applying the first method –6.0 dBm.
  • Page 305 2. Connect data testers to corresponding ports on both the local and remote ETL600 equipment. If there is only one data tester available, the digital data stream has to be looped on the remote equipment.
  • Page 306 AF and frequency response. B.14 Manual reset Reset ETL600 with HMI600 (Equipment / Reset) or by switching off and on the power and wait until all alarms disappear.
  • Page 307 Firmware Download for ETL600 1KHW001496-EN Technical Data ETL600 1KHW001498-EN We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd Form 1KHW001493-EN Rev. A...
  • Page 309 Revision: Language: Page: ETL600 System Settings A1/A4 Item to be Selected programmed or alternative or Action Rack or Remarks fitted setting module General Create a configuration file using HMI600 HMI600 Racks and assemblies A.3.1 Number of P7LA racks Configuration file shows the correct...
  • Page 310 Revision: Language: Page: ETL600 System Settings A2/A4 Item to be Selected programmed or alternative or Action Rack or Remarks fitted setting module A.4.3 Settings for RF hybrid P3LE Jumpers set according to P3LE Jumpers LNx, configuration file Nx, Mx, Hx, Sx...
  • Page 311 Revision: Language: Page: ETL600 System Settings A3/A4 Item to be programmed or Action Rack or Selected alternative or setting Remarks fitted module Settings for NSD600 Interface G4AI, if present A.6.1 Tripping of the inputs Input 1 G4AI Jumper plug N11 N22 N28 N34 N54 N65 N71...
  • Page 312 Revision: Language: Page: ETL600 System Settings A4/A4 Item to be programmed or Action Rack or Selected alternative or setting Remarks fitted module Check board type at slot Configuration file shows Config Compare correct type of board at slot file with...
  • Page 313 Revision: Language: Page: ETL600 System Test Report B1/B11 Test Permissible Test Test procedure Test point value Units result General B.1.1 Visual checks Correct wiring of protective earth P7LA, P7LC PE wired Correct wiring of power supply P7LA, P7LC polarity ok...
  • Page 314 Revision: Language: Page: ETL600 System Test Report B2/B11 Test Permissible Test Test procedure Test point value Units result B.5.4 Adjust Tx alarm level Dialog box: Adjust Tx alarm level Click Activate Tx alarm level, set LED to be ON jumper CH and turn...
  • Page 315 Revision: Language: Page: ETL600 System Test Report B3/B11 Test Permissible Test Test procedure Test point value Units result B.6.5 Link alarm indication Activate link alarm by interrupting RF Link alarm LED on P4LT LED to be ON connection. State of Link alarm relay after...
  • Page 316 Revision: Language: Page: ETL600 System Test Report B4/B11 Test Permissible Test Test procedure Test point value Units result Testing of NSD600 / G4AI, if present B.9.1 Inputs Input 1 IN1 Terminal, U1, see N11N22N28N34N54N65N71 Activate Input 1 (T…/1) – (T.../2)
  • Page 317 Revision: Language: Page: ETL600 System Test Report B5/B11 Test Permissible Test Test procedure Test point value Units result B.9.4 Command transmission time Command A Terminal: Refer HMI600 TPE1 TPE2 Tx command A (T22/1) – (T22/2) Mean value (T…/...) – (T.../…) ≤T0...
  • Page 318 Revision: Language: Page: ETL600 System Test Report B6/B11 Test Permissible Test Test procedure Test point value Units result B.10.3 Remote subscriber. At Mark if configured: remote equ. is Pax 2-Wire Test Ringer: Feed Feed into rem. equ. at Subscriber must...
  • Page 319 Revision: Language: Page: ETL600 System Test Report B7/B11 Test Permissible Test Test procedure Test point value Units result B.10.6 Pax 4-wire. At remote Mark if configured: equ. is Pax 4-wire Test E-Wire: Terminal, telephony E-Wire must 3a-3b toggle Close and open at Remote equ.
  • Page 320 Revision: Language: Page: ETL600 System Test Report B8/B11 Test Permissible Test Test procedure Test point value Units result B.10.8 Pax 4/2-wire Mark if configured: Test E-Wire: Terminal, telephony E-Wire must Close and open at 3a-3b toggle Remote equ. at terminal,...
  • Page 321 Revision: Language: Page: ETL600 System Test Report B9/B11 Test Permissible Test Test procedure Test point value Units result B.10.9 Transit mode for Mark if configured: E&M wire Test E-Wire: Terminal, telephony E-Wire must 3a-3b toggle Close and open at Remote equ. at terminal, telephony 4a-4b B.10.10 Testing the...
  • Page 322 Revision: Language: Page: ETL600 System Test Report B10/B11 Test Permissible Test Test procedure Test point value Units result B.10.14 Teleoperation AF4 Mark if configured: N11 N22 N34 N54 N65 [ ] [ ] [ ] [ ] [ ] Fed input level, [dBm],...
  • Page 323 Revision: Language: Page: ETL600 System Test Report B11/B11 Test Permissible Test Test procedure Test point value Units result B.12.6 V.24 Port 6 Front plate P4LT/P4LU BER test V.24 PORT 6 No bit errors during ____ sec B.13 Documentation Make a printout of...
  • Page 325 Note: • Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd...
  • Page 326 None (no equalizer) The equalizer is bypassed. This setting is working during first power up of the ETL600 equipment until instructed personnel measures the channel and chooses another equalizer. There is no added system delay. This is the best possible value for the system group delay. Note that the operation mode 'Amplitude response equalization only' or 'Combined group delay and frequency response equalization' has no effect in this case.
  • Page 327 Revision: Language: Page: 1KHW001494-EN equalization' enabled only (in 'Configuration' / 'System' / 'Channel Settings'). The default setting is 'Amplitude response equalization only' enabled. Always check the amplitude response of the short equalizer in the pilot channel if used in conjunction with external protection system before activation through instructed personnel. Medium equalizer The medium equalizer compensates the amplitude response of the channel with additional delay.
  • Page 328 By pressing the 'Cancel' button, no channel measurement will be started. By selecting the 'Yes' button, a channel measurement on channel X from the remote to the local ETL600 terminal will be started. This is also the last chance to abort an equalizer selection process without interrupting normal services.
  • Page 329 Please note that after downloading the new settings, the equipment is reset in order to activate the new equalizer. This leads to a short interruption of services on the whole ETL600 link, not only of the affected channel.
  • Page 330 Recommended procedure to equalize a channel Logon to the desired ETL600 using the HMI600 dialog 'Equipment' / 'Connect' with 'Read & Write access' enabled, correct Equipment ID, correct password and with the checkbox 'Upload configuration' selected.
  • Page 331 The connections for the tests can be made either at the test sockets on the front of the equipment or at the terminals. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd...
  • Page 332 Equipment Lower frequency, usually meant as low cut-off frequency Light Emitting Diode found on the front panel HMI600 User Interface Program for ETL600 running on a PC N11, …, N71 Position in rack. Slot number N11, …, N71 Receiver Transmitter Personal Computer X11, …, X71...
  • Page 333 Commissioning Instructions for the ETL600 Rel.1 Equipment General Most of the commissioning tests (including fully automatic equalization) for the ETL600 system can be done with the help of PC based software HMI600. It is assumed, that all assembled Tx filters and Rx filter are tuned.
  • Page 334 Start the HMI600, open the preconfigured file and connect to the equipment as described in the instruction manual, 1KHW001489, chapter 4, section ‘Communication to the ETL600’. On the File menu click New. This opens the Connect dialog box. Click Logon, Equipment ID, with ID 0.
  • Page 335 Revision: Language: Page: 1KHW001495-EN 5/28 Transmitter The Tx RF level and the Tx alarm threshold levels were adjusted during final testing in the works. They need to be changed only if the return loss is too low. C.5.1 Adjust Tx RF level The Tx RF level is adjusted using the HMI600, a level meter and a termination resistor or attenuator.
  • Page 336 ⎠ Lower edge frequency of the nominal Tx band of the local transmitter of the i-th parallel link, if this band is above the frequency band of the local ETL600 receiver Upper edge frequency of the nominal Tx band of the local transmitter of the...
  • Page 337 Note: The tuning is not necessary when the ETL600 is operated without Rx filter P4RX. In this case, default settings must be used: Jumpers RA, LP, CD and CE set and the remaining C-jumpers in P position.
  • Page 338 Check signal to noise ratio (SNR) of the pilots of the configured APLC channels. Equalization Refer to 1KHW001494 ‘APLC Channel Equalization for ETL600’. The document is put into a short instruction, printed in the following chapters C.7.1 and C.7.2. Note: The equalization routine can also be done at the remote equipment via EOC communication.
  • Page 339 Select the new equalizer: In the field New equalizer, activate checkbox Amplitude response equalisation only. External teleprotection equipment connected to ETL600 suffer from the additional delay introduced by the equalizer. To reduce this delay, select type None or Short in the frame New equalizer of the dialog box Select equalizer.
  • Page 340 Revision: Language: Page: 1KHW001495-EN 10/28 C.9.2 Test external real time clock synchronisation, if available The external clock source with IRIG-B format has to be connected to the IRIG-B port at the frontplate of P4LT/P4LU via external cable V9OV. Testing the external synchronisation using HMI600: Set the time on the PC a few hours back/forward On the Equipment menu point to Commissioning and maintenance menu point to Eventrecorder and click Set Clock.
  • Page 341 Revision: Language: Page: 1KHW001495-EN 11/28 Note: The measured transmission time (T ) does not include the channel delay. nominal Note: The nominal transmission time as given in the instruction manual shall serve as a guideline for the mean value of several commands. Get the link to normal operation as described in chapter C.1.
  • Page 342 Revision: Language: Page: 1KHW001495-EN 12/28 C.11.4 Pax 2-wire The following test must only be done, if the operation mode ‘Pax 2-wire’ is configured. Get the equipment in local loop operation according to chapter C.1. Relevant AF measurements cannot be achieved at the 2-wire interfaces in the local loop mode. Check PAX-BLOCKING relay.
  • Page 343 Revision: Language: Page: 1KHW001495-EN 13/28 Toggling the M-WIRE input, E-WIRE output should toggle simultaneously. Note, E-WIRE is a switching contact without inherent voltage source and without polarity. C.11.8 Testing the teleoperation ports For testing the teleoperation ports, first nominal signal levels must be fed into the teleoperation input port with a level generator.
  • Page 344 2. Connect data testers to corresponding ports on both the local and remote ETL600 equipment. If there is only one data tester available, the digital data stream has to be looped on the remote equipment.
  • Page 345 Save the 'et6' file on a disk with the Serial No. of ETL coded in the file name. e.g.HE400327C0.et6. C.15 Manual reset Reset ETL600 with HMI600 (Equipment / Reset) or by switching off and on the power and wait until all alarms disappear.
  • Page 347 Firmware Download for ETL600 1KHW001496-EN Technical Data ETL600 1KHW001498-EN We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd Form 1KHW001495-EN Rev. A...
  • Page 349 Revision: Language: Page: ETL600 Commissioning Report C1/C10 Test Permissible Test Test procedure Test point value Units result General C.1.1 Checking the line of communication Line attenuation Return loss A C.1.2 Visual checks Proper wiring of protective earth P7LA, P7LC PE wired...
  • Page 350 Revision: Language: Page: ETL600 Commissioning Report C2/C10 Test Permissible Test Test procedure Test point value Units result Transmitter C.5.1 Adjust Tx RF level Dialog box: Adjust Tx RF level RF line monitor on RF value indicated Click Start or Set...
  • Page 351 Menu: Equipment, Commissioning and maintenance, Eventrecorder, Set clock Download date/time to RTC Dialog box Actual time and date The tuning is not necessary when the ETL600 is operated without Rx filter P4RX. © ABB Switzerland Ltd Form 1KHw001495-EN Rev. A...
  • Page 352 Revision: Language: Page: ETL600 Commissioning Report C4/C10 Test Permissible Test Test procedure Test point value Units result C.9.2 Test external real time clock synchronization, if available Menu: Equipment, Commissioning and maintenance, Eventrecorder, Set clock Download date/time to RTC Dialog box...
  • Page 353 Revision: Language: Page: ETL600 Commissioning Report C5/C10 Test Permissible Test Test procedure Test point value Units result C.10 NSD600 / G4AI, if present C.10.1 NSD600 loop test TPE1 TPE2 Check Actual transmission time T HMI600 < 2*T0 _______ _______ Link...
  • Page 354 Revision: Language: Page: ETL600 Commissioning Report C6/C10 Test Permissible Test Test procedure Test point value Units result C.11 Testing of O4LE Mark if configured: C.11.1 Service Phone. Pick up the phones and Service phone, at Talk is possible talk. front panel...
  • Page 355 Revision: Language: Page: ETL600 Commissioning Report C7/C10 Test Permissible Test Test procedure Test point value Units result Mark if configured: C.11.5 Pax 4-wire Terminal, telephony Test E-Wire: E-Wire must toggle 3a-3b Close and open at Remote equ. at terminal, telephony 4a-4b Measure Output level.
  • Page 356 Revision: Language: Page: ETL600 Commissioning Report C8/C10 Test Permissible Test Test procedure Test point value Units result PAX-BLOCKING normal Measure at terminal, 6a-6b is open telephony 6a-6b, 6b-7a is closed 6b-7a PAX-BLOCKING Measure at terminal, 6a-6b is closed blocked telephony 6a-6b,...
  • Page 357 Revision: Language: Page: ETL600 Commissioning Report C9/C10 Test Permissible Test Test procedure Test point value Units result Mark if configured: C.11.11 Teleoperation AF3 N11 N22 N34 N54 N65 [ ] [ ] [ ] [ ] Fed input level, [dBm],...
  • Page 358 Revision: Language: Page: ETL600 Commissioning Report C10/C10 Test Permissible Test Test procedure Test point value Units result C.13 V.24 ports Front plate P4LT/P4LU C.13.1 V.24 Port 1 BER ≤ 10 BER test V.24 PORT 1 during ____ sec Front plate P4LT/P4LU C.13.2...
  • Page 359 Note: • Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600. We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. © ABB Switzerland Ltd...
  • Page 360 In this case a configuration download is not possible. The automatic release detection doesn’t detect if you are using the latest release. For information about available releases and about compatibility between software, firmware and hardware of the ETL600 system please refer to the document „Compatibility Requirements for ETL600“ (1KHW001490).
  • Page 361 If your PC is connected to the RS-485 station bus, all ETL600 terminals except one have to be disconnected or switched off for that purpose. Normally the PC is therefore connected directly to the HMI interface (RS-232) on the front plate of the ETL600 terminal to be updated.
  • Page 362 Revision: Language: Page: 1KHW001496-EN Firmware download parameters The Firmware download dialog box contains a field with download parameters. You can choose either an automatic firmware download or a user controlled firmware download by deactivating the check box. 2.4.1 Automatic firmware download This is the recommended method to download the firmware.
  • Page 363 Revision: Language: Page: 1KHW001496-EN 14. The Testconfiguration time dialog box has been opened by the HMI600. Click OK. 15. The HMI600 now compares the equipment identification from the file with the identification stored in the equipment. If it is different, a warning message box appears. Click OK.
  • Page 364 Revision: Language: Page: 1KHW001496-EN Click No to select other files. This opens a file open dialog box for each kind of download file. Click Cancel to stop firmware download. Wait until the Close button changes to the active state. Click Close to leave the firmware download dialog box. Download the modified configuration.
  • Page 365 Revision: Language: Page: 1KHW001496-EN Unsuccessful or incomplete firmware download to a module of type P4LT/P4LU and the HMI600 informs you to execute a firmware download On the File menu click New. This opens the Connect dialog box. Click Logon, Equipment ID: 0 Click Read &...
  • Page 367 Deviation of level measured at the socket “RF line monitor” of P3LE....2 Purpose This document describes the currently known anomalies in the behaviour of the ETL600 Rel.1 system. Such anomalies express themselves in unexpected system behaviour not described in the instruction manual ETL600 Rel.1 (1KHW001489-EN), Edition November 2005.
  • Page 368 Revision: Language: Page: 1KHW001497-EN Anomalies For each anomaly, the following information is given: the types of the hardware modules and/or the versions of firmware or software taken to be responsible for the observed anomaly, a description of the anomaly, a workaround (if any). Deviation of level measured at the socket “RF line monitor”...
  • Page 369 ABB Switzerland Ltd e-mail: utilitycommunication@ch.abb.com Power Technology Systems utilitycommunication@ABB_CH01 PTUKK4 Repair Center Fax: ++ 41 58 585 16 85 CH-5400 Baden / Switzerland Tel: ++ 41 58 589 22 71 Repair & Return Procedure 1) General All our equipment and parts are warranted against defects in material and workmanship for a period as agreed in the order or in the SERVICE CONTRACT.
  • Page 370 ABB Switzerland Ltd e-mail: utilitycommunication@ch.abb.com Power Technology Systems utilitycommunication@ABB_CH01 PTUKK4 Repair Center Fax: ++ 41 58 585 16 85 CH-5400 Baden / Switzerland Tel: ++ 41 58 589 22 71 Repair & Return Procedure (continued) 3) Guide to Complete Fault Report •...
  • Page 371 ABB Switzerland Ltd e-mail: utilitycommunication@ch.abb.com Power Technology Systems utilitycommunication@ABB_CH01 PTUKK4 Repair Center Fax: ++ 41 58 585 16 85 CH-5400 Baden / Switzerland Tel: ++ 41 58 589 22 71 Fault Report A separate “Fault Report” must be completed for each individual faulty item you intend to return to PTUKK4.
  • Page 373 Quality of response Short response time to customers Clear pricing of services Single Point-of-Entry to ensure process efficiency and reliability ABB Switzerland Ltd 02-01-17 1KHM010297Rev.A...
  • Page 375 ETL600 Rel.1 ETL600 complies with EMC Directive 89/336/EEC and the Low-Voltage Directive 73/23/EEC. ETL600 complies with or exceeds the requirements according to IEC publication 60495, second edition, Sept. 1993, with reference to single sideband PLC equipment. The integrated teleprotection equipment NSD600 complies with or exceeds the requirements according to IEC publication 60834-1 "Teleprotection Equipment of Power Systems - Performance...
  • Page 376 Technical Data ETL600 Rel. 1 ABB Switzerland Ltd AUDIO FREQUENCY SERVICES Application Transparent transmission of analog voice-frequency signals like speech, teleoperation, VFT-modems, facsimile. Number of channels Up to 3 AF channels with 4 kHz bandwidth each, or 3 channels of 3.2, 2.4 and 2.4 kHz bandwidth respectively, in 8 kHz total bandwidth For the transparent transmission of speech plus superimposed teleoperation signals ≈...
  • Page 377 Technical Data ETL600 Rel. 1 ABB Switzerland Ltd Broadband data (MOD600) Application Transmission of high-speed / high capacity data in bandwidth of 4 kHz or higher. Number of integrated broadband modems Transmission bandwidth 4, 8, 12, 16, 20, 24, 28, 32 kHz Programmable data rates 9.6, 12, 14.4, 16, 19.2, 24, 28.8, 32, 36, 38.4, 40, 48, 56, 64,...
  • Page 378 Address range for up to 65’000 terminals Alarm polling facility for all terminals in the network, via EOC Firmware download and equipment settings local and remotely via Embedded Operation Channel (EOC) Support of mixed ETL500 / ETL600 networks AMBIENT CONDITIONS Operation Climatic conditions...
  • Page 379 We constantly endeavour to improve the quality of our technical publications and would like to hear your suggestions and comments. Would you therefore please fill in this questionnaire and return it to the address given below. ABB Switzerland Ltd Power Technology Systems Utility Communications, PTUKT...
  • Page 381 IMPORTANT NOTICE! Experience has shown that reliable operation of our products is assured, providing the information and recommendations con- tained in this Instruction Manual are adhered to. It is scarcely possible for the instructions to cover every eventu- ality that can occur when using technical devices and systems. We would therefore request the user to notify us directly or our agent of any unusual observations or instances, in which these instructions provide no or insufficient information.
  • Page 382 CH-5400 Baden / Switzerland Phone +41 58 589 37 35 +41 58 585 16 85 E-mail utility.communications@ch.abb.com www.abb.com/utilitycommunications The Industrial wordmark and all mentioned product names in the form XXXXXX are registered or pending trademarks of ABB Printed in Switzerland (0511-0000-0)

Table of Contents