ABB ETL600 Instruction Manual page 364

Digital power line carrier system
Table of Contents

Advertisement

Revision:
A
Click No to select other files. This opens a file open dialog box for each kind of download file.
Click Cancel to stop firmware download.
7.
Wait until the Close button changes to the active state.
8.
Click Close to leave the firmware download dialog box.
9.
Download the modified configuration. Please refer to paragraph 3.1 step 12.
3.4
Extend the equipment and the HMI600 informs you about firmware
incompatibilities
1.
On the File menu click New. This opens the Connect dialog box.
2.
Click Logon, Equipment ID: 0
3.
Click Read & Write access.
4.
Click Upload configuration.
5.
Click OK. This opens a HMI600 child window.
6.
On the Configuration menu click Services and choose new services.
7.
On the File menu click Save. This opens the Save as dialog box. Click Save.
8.
Close the HMI600 window (File, Close).
9.
Switch off the equipment.
10. Plug in the new modules.
11. Switch on the equipment.
12. On the File menu click Open. This opens the Open dialog box. Select the previously saved
configuration file and click Open.
13. From the Equipment menu click Connect. This opens the Connect dialog box.
14. Click Read & Write access.
15. Click OK.
16. From the Equipment menu click Download configuration. This process automatically
checks the firmware compatibility of the new modules. If an incompatibility is detected proceed
with chapter 3.3. If not, the firmware is fully compatible to the other modules in the equipment.
3.5
Exchange a module and the HMI600 informs you about firmware
incompatibilities
If you have to exchange a module in case of any damage, switch off the equipment, replace the
new module and switch it on again. You can use the last configuration stored in a file to update the
equipment configuration.
The following steps describes the connect and configuration download process with the HMI600.
1.
On the File menu click Open. This opens the Open dialog box. Select the configuration file
and click Open.
2.
From the Equipment menu click Connect. This opens the Connect dialog box.
3.
Click Read & Write access.
4.
Click OK.
5.
From the Equipment menu click Download configuration. This process automatically
checks the firmware compatibility of the replaced module. If an incompatibility is detected
proceed with chapter 3.3. If not, the firmware is fully compatible to the other modules in the
equipment.