ETL600
Appreciable discrepancies between the measured results and the
nominal characteristic point to defective components and the filters
must be checked individually.
SELECTIVE LEVEL
METER SPM 32/33
impedance
appr. 5 kOhm
Output
impedance
approx. 10 Ohm
GENERATOR PS 33
Instruments:
1.
Signal generator
2.
Selective level meter
Fig. 7-1
Phase-to-ground
CF
BT
Z0
Z
Fig. 7-2
Commissioning
1KHW001489-EN
Input
Rec.
Gen.
measuring bridge
Instruments and test circuit for measuring return loss
CF
R e t u r n
lo s s
a
r
coupling filter
balancing transformer
nominal impedance
actual input impedance
Test circuit for measuring return loss under practical
conditions with the transmission line as load
R
N
R
X
Return loss
e.g.:
Acterna PS 33
Acterna SPM 32/33
Phase-to-phase or between line circuits
Z0 + Z
a = 20 log
r
Z0 - Z
November 2005
ABB Switzerland Ltd
Dummy load
Nominal output
impedance:
e.g. 75 Ohm
Coaxial cable
to coupling unit
CF
CF
BT
R e tu rn
lo s s
a
r
7-5