Tuning Instructions for Rx RF Filter P4RX <ETL600 Rel.1>
Responsible Department:
Prepared:
PTUKT
2005-07-05 H. Hoitink
Valid for:
Derived from:
1KHL015117-EN
Powerline Carrier Equipment: Series ETL600
Tuning Instructions for Rx RF Filter P4RX <ETL600 Rel.1>
Contents
1
General ........................................................................................................... 2
2
Programming .................................................................................................. 2
2.1
3
Tuning the filter circuits individually ................................................................ 3
3.1
4
Checking the gain and frequency response of the filter ................................. 4
4.1
4.2
5
Test circuits..................................................................................................... 6
Test conditions:
Temperature range: 10 °C to 40 °C.
List of test equipment:
PC with Windows 2000 or XP
HMI600 software
PC
P4LT cable
Tx tuning adapter P3LL
Rx tuning adapter P4LM
RF test cable 50 Ohm V9MW, BNC to
SSMB (mini coax), 2 cables required
Level meter, wide band or selective,
10 kHz to 1 MHz.
Preferably 50 Ohm input, 75 Ohm may also
be used
Plastic tuning screwdriver
Notes:
Level measurements during tuning & checking frequency response of P4RX are relative. Hence any ordinary
wide band or selective level meter with a frequency range 10 kHz to 1000 kHz can be used. Normally a wide
band level meter will be sensitive enough. If more sensitivity is required, use a selective one. Be careful when
using a wide band meter, as unwanted signals may disturb the measurement.
The same Rx tuning adapter P4LM used for ETL 41 and ETL500 can be used for ETL600. However, if two
shorting wires are present on the P4LM, they must be removed. The position of these 2 shorting wires - if
present - will be across C1-C9 & C2-C10, under the sub-board.
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. © ABB Switzerland Ltd
ABB Switzerland Ltd
Approved:
2005-11-16 H. Benninger
Replaces:
-
Steps for tuning the coils L1 and L2 ..................................................... 3
Steps to check the gain setting ............................................................ 4
Steps to check the frequency response ............................................... 5
Archive No.:
-
Distribution:
-
Classification-No.:
File:
1KHW001491ae Tuning Instructions
for Rx RF Filter P4RX.doc
1:1 serial RS-232
HENF209668
HENF209665
1KHL015238R0001
SPM-33A (Acterna) or equivalent;
featuring both wide band as well as
selective measurements
1KHW001491-EN
Rev.
Date:
A
05-11-16
Lang.:
Page:
EN
1/7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents