Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 577

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

• The EFCALL(P) instruction is used in combination with the ECALL(P) instruction. If the EFCALL(P) instruction is not used
in combination with the ECALL(P) instruction, non-execution processing of the subroutine program is not performed even if
the execution command is turned off, and therefore the output status of each coil instruction is retained.
• When the execution command is turned off, non-execution processing of the subroutine program is performed, enabling the
OUT instruction and PLS instruction (including pulse conversion instructions) to be forcibly turned off.
Ex.
When the EFCALL (P) instruction is used
X0
ECALL
"ABC"
EFCALL
"ABC"
[ABC.PRG]
P0
X1
SET
PLS
(1) Forced off by the EFCALL instruction
Ex.
When the EFCALL (P) instruction is not used
X0
ECALL
"ABC"
[ABC.PRG]
P0
X1
SET
PLS
P0
P0
X0
END
X1
Y10
FEND
Y10
Y11
M0
Y11
M0
RET
END
P0
X0
END
X1
FEND
Y10
Y10
Y11
Y11
M0
M0
RET
END
(1)
7 APPLICATION INSTRUCTIONS
7.4 Structure Creation Instructions
7
575

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents