7.27

Module Access Instructions

Performing I/O refresh

RFS(P)
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These instructions refresh the n points of data from the specified device, and import external inputs or outputs data to the
output module.
Ladder
(s)
(n)
FBD/LD
EN
ENO
s
n
■Execution condition
Instruction
RFS
RFSP
Setting data
■Descriptions, ranges, and data types
Operand
Description
(s)
Start device to be refreshed
(n)
Number of refreshed points
EN
Execution condition
ENO
Execution result
*1 Only labels assigned to devices (X, Y) can be used.
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, SB,
FX, FY
*1
(s)
(n)
*1 Only X and Y can be used.
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=RFS(EN,s,n);
ENO:=RFSP(EN,s,n);
Range
Data type
Bit
1 to 4096
16-bit unsigned binary
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
7 APPLICATION INSTRUCTIONS
Data type (label)
*1
ANY_BOOL
ANY16
BOOL
BOOL
Constant
Others
specification
K, H E
$
7.27 Module Access Instructions
7
1039

Hide quick links:

Advertisement

Table of Contents
loading