Processing details
• These instructions reset the (n) points of bit devices starting from the bit device specified by (d).
• The following table lists the reset status of the bit devices.
Device
Annunciator (F)
Timer (T), retentive timer (ST), counter
(C), long timer (LT), long retentive timer
(LST), long counter (LC)
Bit devices other than the above
• When the specified device is off, the device status does not change.
Operation error
There is no operation error.
Status
• The (n) points of data starting from the annunciator (F) number in the device specified by (d) turn off.
• The annunciator numbers that turned off are deleted from SD64 to SD79, and the remaining data are
compressed forward.
• The number of annunciators stored in SD64 to SD79 is stored in SD63.
• The (n) points, starting from the timer (T), retentive timer (ST), counter (C), long timer (LT), long retentive timer
(LST), or long counter (LC) number in the device specified by (d), of current values are reset to 0, and the (n)
points of coils and contacts are turned off.
• The (n) points, starting from the device specified by (d), of coils and contacts are turned off.
6 BASIC INSTRUCTIONS
6.4 Bit Processing Instructions