Hour meter

HOURM
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
• The RnCPU and RnENCPU with firmware version "17" or later support this instruction. (Use an engineering tool with version "1.020W" or later.)
This instruction measures the period of time for which the start contact is ON in units of hour, and turns on the device specified
by (d2) when the accumulated ON time reaches the time (16-bit binary data) specified in (s).
Ladder
(s)
(d1) (d2)
FBD/LD
EN
ENO
s
d1
d2
■Execution condition
Instruction
HOURM
Setting data
■Description, range, data type
Operand
Description
(s)
Time after which the alarm (d2) is set to on (unit: hour)
(d1)
Device where the measured current value is stored
(d2)
Device to be turned on when a timeout occurs (alarm
output)
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, SB,
FX, FY
*1
(s)
(d1)
(d2)
*1 FX and FY cannot be used.
*2 T, ST, C, and FD cannot be used.
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
*2
ST
ENO:=HOURM(EN,s,d1,d2);
Range
Data type
0 to 32767
16-bit signed binary
16-bit signed binary
Bit
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
7 APPLICATION INSTRUCTIONS
Data type (label)
ANY16
ANY16_ARRAY
(Number of elements: 2)
ANY_BOOL
BOOL
BOOL
Constant
Others
specification
K, H E
$