Processing details
• These instructions convert the 32-bit signed binary data in the device specified by (s) to 16-bit unsigned binary data, and
store the converted data in the device specified by (d).
The following program example converts, when M0 turns on, the 32-bit signed binary data stored in D0 and D1 to 16-bit
unsigned binary data, and stores the converted data in D100.
SM402
M0
(1) Data before conversion is stored in the lower 16 bits.
Operation error
There is no operation error.
(s)
D1, D0
DMOVP
H87654321
D0
(s)
(d)
DINT2UINT
D0
D100
b31
∙∙∙
b16
b15
∙∙∙
b0
8765H
4321H
(-2023406815)
(d)
b15
∙∙∙
b0
D100
4321H
(17185)
(1)