Annunciator
OUT F
RnPCPU
RnCPU RnENCPU
(Process)
This instruction outputs the operation result up to the OUT F instruction to the specified annunciator.
Ladder
(d)
FBD/LD
EN
ENO
d
( is to be replaced by OUT.)
■Execution condition
Instruction
OUT F
Setting data
■Description, range, data type
Operand
Description
(d)
Target annunciator number
EN
Execution condition
ENO
Execution result
*1 Only labels assigned to the annunciator can be used.
■Applicable devices
Operand
Bit
X, Y, M, L,
SM, F, B, SB,
FX, FY
*1
(d)
*1 Only F can be used.
Processing details
• This instruction outputs the operation result up to the OUT F instruction to the specified annunciator.
• When the annunciator (F) is turned on by this instruction, the following are performed.
• The USER LED of the CPU module turns on.
• The annunciator number (F number) to be turned on is stored in the special register (SD64 to SD79).
• The value in SD63 is incremented by one.
• If the value in SD63 is 16 (meaning 16 annunciators are already on), the annunciator number will not be stored in the
special register (SD64 to SD79) even when a new annunciator turns on.
• When the annunciator (F) is turned off by this instruction, the following are performed.
• The coil turns off, but the USER LED status and the data in SD63 to SD79 remain unchanged.
• To turn off the USER LED or delete the annunciator number that has been turned off by this instruction from SD63 to SD79, use the RST F instruction.
Operation error
There is no operation error.
5 SEQUENCE INSTRUCTIONS
188
5.3 Output Instructions
RnPCPU
RnSFCPU RnSFCPU
(Redundant)
(Standard)
(Safety)
Execution condition
Every scan
Word
J\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
ST
ENO:=OUT(EN,d);
Range
Double word
U\G, J\,
Z
LT, LST,
U3E\(H)G
LC
Data type
Data type (label)
Bit
ANY_BOOL
Bit
BOOL
Bit
BOOL
Indirect
Constant
specification
LZ
K, H
*1
Others
E
$