Writing Clock Data - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Writing clock data

DATEWR(P)
RnPCPU
RnPCPU
RnCPU RnENCPU
(Process)
(Redundant)
These instructions write the clock data stored in the specified device and later to the clock element of the CPU module.
Ladder
(s)
FBD/LD
EN
ENO
s
■Execution condition
Instruction
DATEWR
DATEWRP
Setting data
■Description, range, data type
Operand
Description
(s)
Start device where the clock data to be written to the clock
element is stored
EN
Execution condition
ENO
Execution result
■Applicable devices
Operand
Bit
X, Y, M, L,
J\
SM, F, B, SB,
FX, FY
(s)
RnSFCPU RnSFCPU
(Standard)
(Safety)
Execution condition
Word
T, ST, C, D, W,
U\G, J\,
SD, SW, FD, R,
U3E\(H)G
ZR, RD
ST
ENO:=DATEWR(EN,s);
ENO:=DATEWRP(EN,s);
Range
Data type
Refer to "Processing
16-bit signed binary
details".
Bit
Bit
Double word Indirect
Z
LT, LST,
LZ
LC
7 APPLICATION INSTRUCTIONS
Data type (label)
ANY16_ARRAY
(Number of elements: 7)
BOOL
BOOL
Constant
Others
specification
K, H E
$
7.25 Clock Instructions
7
1003

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents