Connecting To Su-5M/6M - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

7.5.2

Connecting to SU-5M/6M

■1. Communication settings
Make the following settings using the programmer system parameter setting.
Item
Protocol
Response delay time
Timeout Time
Station No.
Transmission mode
Stop bit
Data bit
Parity
*1
Transmission speed
*1
Indicates only the transmission speeds that can be set on the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to the following.
7.5.3
Connecting to DirectLOGIC 05 series or DirectLOGIC 06 series
■1. Communication settings
Make the following settings using the programmer system parameter setting.
Item
Protocol
Timeout
RTS On Delay Time
RTS Off Delay Time
Station No.
*2
Transmission speed
Stop bit
Parity
Communication format
*1
To use a PLC with multidrop, set the "RTS on delay time" to 5ms or more and the "RTS off delay time" to 2ms or more.
*2
Indicates only the transmission speeds that can be set on the GOT side.
Set the same transmission speed of the GOT.
For the transmission speed setting on the GOT side, refer to the following.
CCM
0ms
800ms/960ms/1200ms/1600ms/4000ms/8000ms/16000ms/40000ms
1 to 90
HEX
1bit, 2bits
8bits (Fixed)
NONE, ODD, EVEN
9600bps, 19200bps, 38400bps
7.4.1 Setting communication interface (Communication settings)
CCM NET (DirectNET)
780ms or more
0ms
0ms
1 to 90
9600bps, 19200bps, 38400bps
1bit, 2bits
NONE, ODD, EVEN
HEX
7.4.1 Setting communication interface (Communication settings)
Set value
Set value
*1
*1
7.5 PLC Side Setting
7
7 - 27