2Communication Detail Settings - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

3.4.2
Communication detail settings
Item
Transmission Speed
Data Bit
Stop Bit
Parity
Retry
Timeout Time
*3*4
Host Address
Delay Time
*2
Format
*1
*2
*3
*4
3 - 58
3.4 GOT Side Settings
Set this item when change the transmission speed used for communication with
the connected equipment.
(Default: 9600bps)
Set this item when change the data length used for communication with the
connected equipment.
(Default: 8bits)
Specify the stop bit length for communications.
(Default: 1bit)
Specify whether or not to perform a parity check, and how it is performed during
communication.
(Default: Even)
Set the number of retries to be performed when a communication error occurs.
(Default: 0time)
Set the time period for a communication to time out.
(Default: 3sec)
Specify the host address (station No. of the GOT to which the temperature
controller is connected) in the connected network.
(Default: 1)
Set this item to adjust the transmission timing of the communication request from
*1
the GOT.
(Default: 1ms)
Select the communication format.
(Default: 1)
format 1: only continuous access
format 2: continuous and random
access
Do not specify "0".
Format is ignored when connecting to DMC50.
Host Address is ignored when connecting to DMC10 or SDC.
Host Address is valid when connecting to DMC50.
Devices to be the target of Host Address setting differ depending on the system configuration.
<When connecting to the temperature controller via COM module>
Specify the station No. of the COM module.
<When connecting to the temperature controller directly>
Specify the station No. of the temperature controller.
Description
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
0 to 5times
1 to 30sec
1 to 15
0 to 300ms
1/2