(5) RS-485 connection diagram 5)
* 3
GOT side
SDA
SDB
RDA
RDB
SG
* 4
RSA
* 4
CSA
* 4
RSB
* 4
CSB
*1
*2
*3
*4
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-485 cable must be 500m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
➠
(3) OMRON temperature controller side connector
Use the connector compatible with the OMRON temperature controller.
For details, refer to the user's manual of the OMRON temperature controller.
■3. Setting terminating resistors
(1) GOT side
Set the terminating resistor setting switch of the GOT main unit to "100 OHM".
For details of terminating resistor settings, refer to the following.
➠
(2) OMRON temperature controller side
When connecting a OMRON temperature controller to the GOT, the terminating resistor must be connected to the
OMRON temperature controller.
➠
5 - 22
5.3 Connection Diagram
Terminating resistor(120Ω 1/2W)
Temperature
* 1
controller side
B(+)
A(-)
Pin No. of temperature controller differs depending on the model. Refer to the following.
Terminating resistor should be provided for a temperature controller and an interface converter which will be terminating resistors.
Set the terminating resistor of GOT side, which will be a terminal, to "110Ω".
➠
1.4.3 Terminating resistors of GOT
E5AN(-H,-HT)
Signal
E5EN(-H,-HT)
name
E5CN(-H,-HT)
Pin No.
A(-)
12
B(+)
11
The signals RSA, RSB, CSA, and CSB are not provided for
1.4.1 GOT connector specifications
1.4.3 Terminating resistors of GOT
User's Manual of the OMRON temperature controller
* 2
Temperature
* 1
controller side
B(+)
A(-)
Model of temperature controller
E5CC(-T)
E5GN
E5ZN
E5EC(-T)
E5AC(-T)
Pin No.
Pin No.
Pin No.
6
24
14
5
23
13
. Return connection is not required.
Temperature
controller side
B(+)
A(-)
E5CC-B
E5DC
E5GC
E5EC-B
Pin No.
Pin No.
Pin No.
19
or
4
8
20
17
or
3
7
18
* 1
E5AR(-T)
E5ER(-T)
Pin No.
2
1