■2. Setting PLC system settings
(1) CJ1, CJ2, CS1
Make the PLC system settings.
Channel
160
161
163
*1
*2
*3
(2) CP1H, CP1L, CP1E
Set the PLC system settings of the option slot connected to the GOT.
Mode
Parameter
*1*2
Baud rate
*3
Unit number
*1
*2
*3
4 - 36
4.2 Serial Connection
Bit
15
8 to 11
3
2
0 to 1
0 to 7
0 to 7
Only transmission speeds available on the GOT side are shown.
Set the same port transmission speed as that of the GOT side.
Set the host link station No. according to the Host Address on the GOT side.
POINT
POINT
POINT
Precautions for changing the PLC system settings
Before changing the PLC system settings, make sure that the switch settings have been
changed as follows:
CJ1, CJ2, CS1: Front panel DIP switch SW5 to "OFF"
Item
Only transmission speeds available on the GOT side are shown.
Set the same port transmission speed as that of the GOT side.
Set the host link station No. according to the Host Address on the GOT side.
POINT
POINT
POINT
Precautions for changing the PLC system settings
Before changing the PLC system settings, check the setting of the front DIP switch
corresponding to the option slot used at the time of communication with GOT.
(3) Setting on the CP1H, CP1L
Item
Arbitrary settings ON/OFF
Serial communication mode
Data bit
Stop bit
Parity
*1*2
Port transmission speed
*3
Host link station No.
Host link
7, 2, E
4800bps,9600bps,19200bps,
38400bps,57600bps,115200bps
00 to 31
Set value
1H: Arbitrary settings (fixed)
0H: Upper link (fixed)
0H: 7bits (fixed)
0H: 2bits (fixed)
0H: Even (fixed)
00H: 9600bps
05H: 4800bps
06H: 9600bps
07H: 19200bps
08H: 38400bps
09H: 57600bps
0AH: 115200bps
0H to 1FH
: No.00 to 31