3.7

Precautions

■1. Station number setting of the temperature controller system
• When connecting to DMC10 or SDC
Make sure to establish temperature controller system with No.1 station.
• When connecting to DMC50 or AHC2001
A COM module or temperature controller with the station number set with the host address must be included.
3.4.2 Communication detail settings
■2. GOT clock control
Since the control equipment does not have a clock function, the settings of "time adjusting" or "time broad cast" by
GOT clock control will be disabled.
■3. Disconnecting some of multiple connected equipment
The GOT can disconnect some of multiple connected equipment by setting GOT internal device. For example, the
faulty station where a communication timeout error occurs can be disconnected from connected equipment.
For details of GOT internal device setting, refer to the following manual.
GT Designer3 (GOT2000) Screen Design Manual
■4. When DMC50/AHC2001 and DMC10/SDC are mixed
GOT does not support connections with DMC50/AHC2001 and DMC10/SDC mixed.
■5. Station number range for AHC2001
The station number for AHC2001 ranges from 1 to 127. However, use station numbers from 1 to 15, which are the
range for DMC50.
■6. Device range for AHC2001
The GOT only supports some devices for the AHC2001.
Use the devices within the device range for the DMC50.
3 - 75
3.7 Precautions
3