Mitsubishi Electric GOT2000 Series Connection Manual page 254

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

■2. Communication detail settings
(1) Ethernet (OMRON), Gateway
Make the settings according to the usage environment.
GOT Net No.
*2
GOT Station
GOT Communication Port No.
Retry
Startup Time
Timeout Time
Delay Time
*1
*2
4 - 52
4.3 Ethernet Connection
Item
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 18)
Set the GOT port No. for the connection with the Ethernet
*1
module.
(Default: 5018)
Set the number of retries to be performed when a
communication timeout occurs. When receiving no response
after retries, the communication times out. (Default: 3times)
Specify the time period from the GOT startup until GOT starts
the communication with the PLC CPU. (Default: 3sec)
Set the time period for a communication to time out. (Default:
3sec)
Set the delay time for reducing the load of the network/
destination PLC. (Default: 0ms)
By setting of the OMRON PLC, set the same [GOT Communication Port No.] setting as that of [FINS UDP Port] of CX-
Programmer.
Each of [GOT Station] set in the communication detail setting and [Station] set in the Ethernet setting must be set to different
station numbers.
➠ ■4.
Ethernet setting
Description
Range
1 to 127
1 to 254
1024 to 5010, 5014 to 65534
(Except for 5011, 5012, 5013
and 49153 to 49170)
0 to 5times
3 to 255sec
1 to 90sec
0 to 10000
( 10ms)