Mitsubishi Electric GOT2000 Series Connection Manual page 562

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

(19) RS-232 connection diagram 19)
*1
*2
(20) RS-232 connection diagram 20)
*1
*2
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.The length of the cable must be 3m or less with a transmission
speed of 38400bps.
(2) GOT side connector
For the GOT side connector, refer to the following.
(3) Connector for Panasonic Industrial Devices SUNX PLC
Use the connector applicable to the Panasonic Industrial Devices SUNX PLC.
For details, refer to the Panasonic Industrial Devices SUNX PLC user's manual.
15 - 32
15.3 Connection Diagram
GOT side
CD
1
RD(RXD)
2
SD(TXD)
3
ER(DTR)
4
SG
5
DR(DSR)
6
RS(RTS)
7
CS(CTS)
8
-
9
The details of the connection on the PLC are shown below.
Communication cassette: AFP7CCS2([5 Wire] is selected)
Connect to the terminal for which the front panel LED of the communication cassette shown in parentheses is ON.
GOT side
(terminal block)
SD
RD
ER
DR
SG
RS
CS
NC
NC
The details of the connection on the PLC are shown below.
Communication cassette : AFP7CCS2([5 Wire] is selected)
Connect to the terminal for which the front panel LED of the communication cassette shown in parentheses is ON.
1.4.1 GOT connector specifications
*1
PLC side
* 2
SD(SD)
* 2
RD(RD)
SG
* 2
RD(RD/C)
* 2
SD(SD/R)
PLC side
* 2
RD(RD)
* 2
SD(SD)
SG
* 2
RD(RD/C)
* 2
SD(SD/R)

Advertisement