(6) Operating condition setting completed flag (X9)
When changing the following settings, use Operating condition setting completed flag (X9) as an interlock
condition to turn on then off Operating condition setting request (Y9).
• Conversion enable/disable setting (Un\G0)
• CH Average time/Average number of times/Moving average/Time constant settings (Un\G1 to Un\G8)
• Averaging process setting (Un\G24, Un\G25)
• Sampling cycle setting (Un\G26)
• Input signal error detection setting (Un\G47)
• Warning output setting (Un\G48)
• Scaling enable/disable setting (Un\G53)
• CH Scaling lower limit value (Un\G62, Un\G64, Un\G66, Un\G68, Un\G70, Un\G72, Un\G74, Un\G76)
• CH Scaling upper limit value (Un\G63, Un\G65, Un\G67, Un\G69, Un\G71, Un\G73, Un\G75, Un\G77)
• CH Process alarm lower lower limit value (Un\G86, Un\G90, Un\G94, Un\G98, Un\G102, Un\G106,
Un\G110, Un\G114)
• CH Process alarm lower upper limit value (Un\G87, Un\G91, Un\G95, Un\G99, Un\G103, Un\G107,
Un\G111, Un\G115)
• CH Process alarm upper lower limit value (Un\G88, Un\G92, Un\G96, Un\G100, Un\G104, Un\G108,
Un\G112, Un\G116)
• CH Process alarm upper upper limit value (Un\G89, Un\G93, Un\G97, Un\G101, Un\G105, Un\G109,
Un\G113, Un\G117)
• CH Rate alarm warning detection period (Un\G118 to Un\G125)
• CH Rate alarm upper limit value (Un\G126, Un\G128, Un\G130, Un\G132, Un\G134, Un\G136, Un\G138,
Un\G140)
• CH Rate alarm lower limit value (Un\G127, Un\G129, Un\G131, Un\G133, Un\G135, Un\G137, Un\G139,
Un\G141)
• CH Input range setting (Un\G150 to Un\G157)
• Mode switching setting (Un\G158, Un\G159)
• Dropout detection setting (Un\G160)
• CH Dropout value (Un\G162 to Un\G169)
• Peak current detection setting (Un\G300)
• CH Peak current detection time (Un\G318 to Un\G325)
• CH Peak current detection value (Un\G326 to Un\G333)
• CH Logging enable/disable setting (Un\G1000 to Un\G1007)
• CH Logging data setting (Un\G1024 to Un\G1031)
• CH Logging cycle setting value (Un\G1032 to Un\G1039)
• CH Logging cycle unit setting (Un\G1040 to Un\G1047)
• CH Logging points after trigger (Un\G1048 to Un\G1055)
• CH Level trigger condition setting (Un\G1056 to Un\G1063)
• CH Trigger data (Un\G1064 to Un\G1071)
• CH Trigger setting value (Un\G1082 to Un\G1089)
82