Error code
Description and the error cause
(decimal)
The set logging cycle is shorter than the update cycle of the
*1
logged value (digital output value or scaling value).
202
The channel where the error has occurred fits in .
CH Logging data setting (Un\G1024 to Un\G1031) is set to a
*1
value other than 0 and 1.
203
The channel where the error has occurred fits in .
CH Logging points after trigger (Un\G1048 to Un\G1055) is
*1
set to a value outside the range of 1 to 5000.
204
The channel where the error has occurred fits in .
CH Level trigger condition setting (Un\G1056 to Un\G1063) is
*1
set to a value outside the range of 0 to 3.
205
The channel where the error has occurred fits in .
CH Trigger data (Un\G1064 to Un\G1071) is set to a value
*1
outside the range of 0 to 4999.
206
The channel where the error has occurred fits in .
CH Logging hold request (Un\G1008 to Un\G1015) is set to a
*1
value other than 0 and 1.
207
The channel where the error has occurred fits in .
*1
These error codes can be cleared by turning on then off Error clear request (YF).
*2
This error code is not stored in Latest error code (Un\G19) but in the completion status of the G(P).OGSTOR instruction
(
+ 1).
S
CHAPTER 11 TROUBLESHOOTING
Action
Set CH Logging cycle setting value (Un\G1032 to
Un\G1039) and CH Logging cycle unit setting
(Un\G1040 to Un\G1047) so that the logging cycle is
equal to or longer than the update cycle of the logged
value.
For the setting procedure of a logging cycle, refer to
the following.
(
• Logging Function
Page 58, Section 4.12)
Set Digital output value (0) or Scaling value (1) in
CH Logging data setting (Un\G1024 to Un\G1031).
Set a value within the range of 1 to 5000 in CH
Logging points after trigger (Un\G1048 to Un\G1055).
Set one of the following values in CH Level trigger
condition setting (Un\G1056 to Un\G1063).
• Disable (0)
• Above (1)
• Below (2)
• Pass through (3)
Set a value within the range of 0 to 4999 in CH
Trigger data (Un\G1064 to Un\G1071).
Set OFF (0) or ON (1) in CH Logging hold request
(Un\G1008 to Un\G1015).
11
227