Details Of I/O Signals; Input Signal - Mitsubishi Electric MELSEC-Q series User Manual

Programmable controller current transformer input module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

5.2

Details of I/O Signals

The following describes the details of the CT input module I/O signals assigned to the CPU modules.
The I/O numbers (X/Y) described below show the case that the start I/O number of the CT input module is set to 0.
5.2.1

Input signal

(1) Module READY (X0)
Module READY (X0) turns on to indicate the preparation for the digital conversion is completed at the power-on or
reset operation of the CPU module.
Module READY (X0) turns off in the following cases.
• When the offset/gain setting mode is set (The digital conversion processing is executed.)
• When a watchdog timer error occurs in the CT input module (The digital conversion processing is not
executed.)
(2) Default setting completed flag (X5)
Use Default setting completed flag (X5) as an interlock condition to turn on then off Default setting request (Y5).
When the buffer memory settings return to the default by turning on Default setting request (Y5), Default setting
completed flag (X5) turns on. When Default setting request (Y5) is turned off, Default setting completed flag (X5)
also turns off.
The buffer memory areas which return to the default value are with
Buffer Memory Addresses (
Default setting request (Y5)
Conversion enable/disable setting
(Un\G0)
Values in
the buffer memory areas
Default setting completed
flag (X5)
Operating condition
setting request (Y9)
Operating condition
setting completed flag (X9)
The setting of buffer memory areas whose default value is read becomes valid by changing the value as necessary and
turning on then off Operating condition setting request (Y9).
78
Page 89, Section 6.1).
ON
OFF
0
(Enable)
Data before the default
setting is completed
ON
OFF
OFF
ON
in the "Set value backup area" in the List of
Controlled by the CT input module
Controlled by the sequence program
OFF
1 (Disable)
Change the default value
Default value
depending on a situation.
OFF
ON
OFF
OFF
ON

Hide quick links: